Viessmann Boiler: Boiler in heating/cooling application
Boiler in heating/cooling application on a Viessmann boiler: When the boiler is used with a refrigeration system, the chilled medium must be piped in parallel with the boiler using valves that keep chilled medium out of the boiler. Air handler heating coils exposed to refrigerated air need flow control valves or other automatic means to stop gravity circulation during cooling. Check the chiller manufacturer's requirements. The circulating pump must run from a separate on/off switch, not the boiler pump aquastat.
Applies to: Boiler connected to a chiller or cooling coils
How to fix boiler in heating/cooling application: step by step
- Label the changeover valves v1 and v2.
- Cooling season: close valve v1 and open valve v2.
- Heating season: close valve v2 and open valve v1.
- Run the circulating pump from a separate on/off switch, not the boiler aquastat.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Vitocrossal 300 CU3A Installation Instructions, p. 52. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.