Viessmann Boiler: Boiler in heating/cooling application with chiller
Boiler in heating/cooling application with chiller on a Viessmann boiler: When the boiler is used with a refrigeration system, the chilled medium must be piped in parallel with the boiler. Valves must stop chilled water from entering the boiler. Coils in air handlers exposed to cooled air need flow control or another automatic means to stop gravity circulation of boiler water during cooling.
Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352
How to fix boiler in heating/cooling application with chiller: step by step
- Pipe the chiller in parallel with the boiler using valves that keep chilled medium out of the boiler.
- Fit a spring-loaded flow check valve and a circulation pump as shown in the layout.
- Run the circulating pump from its own on/off switch, not from the boiler pump aquastat.
- Label the changeover valves v1 and v2.
- Check the chiller manufacturer's installation instructions for any extra requirements.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Viessmann Vitodens 200-W B2HA 80 to 100, 285 to 352 installation manual, p. 44. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.