Viessmann Boiler: Boiler disable external control

Updated · by Aurora Star Tech Inc.

Boiler disable external control on a Viessmann boiler: A dry contact on the plug aVD takes the boiler out of the boiler sequence.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Boiler disable contact

How to fix boiler disable external control: step by step

  1. Connect a dry contact to terminals 1 and 2 of plug aVD.
  2. Contact closed: the burner is disabled, the isolation/return valve closes, and the shunt pump or boiler circuit pump switches off. Other boilers must supply the heat.
  3. Contact open: the boiler returns to the current boiler sequence.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Vitotronic 100, type GC1

Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 51. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.