Viessmann Boiler: Boiler control power supply, 120 VAC single-phase (VD2/VD2A/CT3)
Boiler control power supply, 120 VAC single-phase (VD2/VD2A/CT3) on a Viessmann boiler: Supply the control through a disconnect and overcurrent protection. The main supply must have overcurrent protection rated at most 15 A and a 2-pole disconnect. The control must be grounded, and L, N and G must not be interchanged.
Applies to: VD2, VD2A and CT3 boiler controls on 120 VAC 1PH supply
How to fix boiler control power supply, 120 vac single-phase (vd2/vd2a/ct3): step by step
- Make sure the main supply to the control has overcurrent protection rated at 15 A maximum and a 2-pole disconnect.
- Connect the supply wire to terminals 11, N and G on the DIN rail inside the connection enclosure.
- Confirm the control is grounded.
- Check that L, N and G are not interchanged.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 GC1 installation and service instructions, p. 82. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.