Viessmann Boiler: Boiler control not active (green power LED off)
Boiler control not active (green power LED off) on a Viessmann boiler: The control shows no power. Check the power switch first, then the supply to the control, then the control fuse.
Applies to: Vitotronic 100 KW10B boiler control
Common causes of boiler control not active (green power led off)
- Power switch 8 is in the 0 position
- Main power to the control and heating system is off
- Fuse F1 on the control has blown
How to fix boiler control not active (green power led off): step by step
- Set power switch 8 to the I position.
- Turn on main power and confirm 120 VAC at the control receptacle.
- If the fuse has blown, replace F1 with the same type and rating (T 6.3 A / 250 V, slow blow).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100, KW10B Operating and User's Information manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.