Viessmann Boiler: Boiler activation contact for external modulation controller
Boiler activation contact for external modulation controller on a Viessmann boiler: Wiring and behaviour of the boiler activation dry contact on plug aVH (Vitocrossal 300, CT3).
Applies to: Vitocrossal 300 with external modulation controller
How to fix boiler activation contact for external modulation controller: step by step
- Connect a dry contact across terminals 2 and 3 of plug aVH.
- Contact closed: the preheat function for follow-up boilers runs first (coding 2b). After preheat, burner stages or modulation can be switched externally.
- Contact closed: boiler water temperature is capped by the preset maximum or the mechanical high limit. The set-point is chosen with coding 9b.
- Contact open: the isolation valve closes after about 5 minutes (coding 2C). External burner stage override is not possible and no minimum temperature is held.
- On multi-boiler systems the lead boiler contact must stay closed at all times.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Viessmann Vitotronic 100 GC1 installation manual, p. 64. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.