Viessmann Boiler: Block a lag boiler externally (aVD plug)
Block a lag boiler externally (aVD plug) on a Viessmann boiler: Use the aVD plug to take a boiler out of the sequence from outside the control. Only applies to lag boilers.
Applies to: Vitotronic 300 GW6B, lag boilers, plug aVD
How to fix block a lag boiler externally (avd plug): step by step
- Use a potential-free contact only. A live contact causes short circuits or phase failure.
- To block the boiler, wire the contact to aVD.1/aVD.2 and close it. The boiler is removed from the sequence, the motorized isolation valve closes and the boiler circuit pump stops.
- Check that the other boilers take over the heat load.
- With the contact open, the boiler is integrated back into the sequence.
- To add the boiler as the last one in the sequence, wire the contact to aVD.2/aVD.3 and close it. The boiler is moved from its current position and started last.
- With the contact open, the boiler stays integrated in the current sequence.
- If all boilers are blocked or none is ready, the heating system has no frost protection.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 GW6B installation and service manual, p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.