Viessmann Boiler: Bleed air from boiler heat exchanger
Bleed air from boiler heat exchanger on a Viessmann boiler: Purge air from the boiler heat exchanger by flushing it through the boiler supply and return with isolation valves closed.
Applies to: Vitodens 200-W B2HA 45, 60
How to fix bleed air from boiler heat exchanger: step by step
- Connect a hose from the boiler filling tap to a fresh water supply or heating medium.
- Open the fresh water supply valve, then open the boiler filling tap slowly. Keep isolation valves closed.
- Flush the heat exchanger through supply and return for at least 10 minutes until all air is removed.
- When the drain valve runs water, close the boiler drain valve, then the boiler fill valve, and open the system isolation valves.
- Close the gas shut-off valve and switch the control unit ON.
- Run the venting program from the service menu.
- Check system pressure.
- Confirm adequate fuel supply, then open the gas shut-off valve.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.