Viessmann Boiler: Application Example 5 system layout
Application Example 5 system layout on a Viessmann boiler: One direct-connected boiler circuit without a mixing valve, plus two mixing-valve heating circuits, with a DHW tank. The Vitotronic 300 runs the boiler, the DHW tank and both mixing circuits through the Power Pump Module and the KM-BUS expansion module. A supply check valve is needed only where the boiler return is piped as one common connection.
Applies to: Application Example 5, Vitotronic 300 with two mixing-valve circuits
How to fix application example 5 system layout: step by step
- Fit the Vitotronic 300 with the Power Pump Module and the KM-BUS expansion module.
- Connect mixing valve 1 and mixing valve 2 through their actuator accessory kits, with the supply sensor in each kit.
- Wire the DHW tank sensor and the DHW pumps to their connections.
- Fit a supply check valve only if the boiler return is one common connection.
- Connect the return water sensor only where the design needs it, for example underfloor heating that controls supply and return temperature.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 installation instructions, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.