Viessmann Boiler: Application 5: low-temperature HC2 with 3-way mixing valve plus high-temperature ZC1
Application 5: low-temperature HC2 with 3-way mixing valve plus high-temperature ZC1 on a Viessmann boiler: A low-temperature heat circuit uses a 3-way mixing valve and a high-temperature zone circuit ZC1. Space heating and DHW can run at the same time, so size the boiler accordingly. A ZC1 call turns on the 28/20 plug pump. The HC2 mixing valve follows the heating curve set in the boiler control.
Applies to: Application code VD2T 2HC2T2ZP.02 and VD2T 2ZC/HC2T2ZP.02 (Application 5, pages 42-44)
How to fix application 5: low-temperature hc2 with 3-way mixing valve plus high-temperature zc1: step by step
- Wire the mixing valve module as shown in the wiring reference (page 17 of the manual, not included here).
- Connect the zone thermostats to the DE connections. Vitotrols can replace the thermostats.
- Include the jumper between the 40A plug and the 157 plug.
- Wire the outdoor sensor and low-loss header sensor as shown.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
222-F B2TB 19222-F B2TB 35222-F B2TB 68222-F B2TB 125B2TB 19B2TB 35B2TB 68B2TB 125VD2T 1HC1T4ZP.01VD2T 1HC1T4ZV.01Vitodens 222-F, B2TB 19Vitodens 222-F, B2TB 35Vitodens 222-F, B2TB 68Vitodens 222-F, B2TB 125
Source: Viessmann Vitodens 222-F B2TB application guide, p. 42-44. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.