Viessmann Boiler: Application 3: single fixed-setpoint zone with no pump output
Application 3: single fixed-setpoint zone with no pump output on a Viessmann boiler: Single-temperature zone. A thermostat call goes through the multi-zone control to the DE1 input of the EA1 boiler, which then runs a fixed zone setpoint. No pump is assigned to this zone.
Applies to: Application 3, one zone circuit, no pump output
How to fix application 3: single fixed-setpoint zone with no pump output: step by step
- In the zone control wizard, select 1 Zone Circuit and press OK.
- Confirm the fixed setpoint choice and press OK.
- Leave the pump unassigned. Pressing OK without choosing an output assigns no pump.
- Check that the zone circuit summary shows no pumps selected.
- Finish start-up when the boiler reports it is ready.
- Set the target water temperature for a heat call with the arrow keys and press OK.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Vitocrossal 300 CU3A Application Guide, p. 28. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.