Viessmann Boiler: Annual service: safety, controls and water system checks
Annual service: safety, controls and water system checks on a Viessmann boiler: Annual checks by the heating contractor covering high limits, low water cut-off, pressure relief, water quality and the door switch.
Applies to: VD2A-125 to VD2A-270
How to fix annual service: safety, controls and water system checks: step by step
- Test the safety high limits.
- Test the high limits by setting them lower and switching the burner on and off to confirm they work.
- Test the low water cut-off and verify it operates per the manufacturer's instructions.
- Check and flush the low water cut-offs (float type) during operation, following the supplier's instructions.
- Check the pressure relief valve and system pressure, and verify the automatic feed if installed.
- Test and establish the proper chemical makeup of the system water.
- Check the heating pipe joints, valves and air vents; correct any leaks immediately and find the cause.
- Make sure the door safety switch operates properly.
- If a circulating pump is field-installed or already present, check its maintenance or lubrication requirements per the pump manufacturer.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200 VD2A service instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.