Annual service by heating contractor on a Viessmann boiler: Performed by a qualified heating contractor or service agency at least once a year.
Applies to: All VD2 sizes 320 to 1080
Common causes of annual service by heating contractor
- Deficiencies not corrected in time
- Leaks in pipe joints, valves or air vents
- Chemicals or combustibles stored too close to the boiler
How to fix annual service by heating contractor: step by step
- Test the safety high limits and the burner with its accessories.
- Test and establish proper chemical makeup of system water.
- Check flue pipe, chimney connection and chimney.
- Check the pressure relief valve, system pressure and automatic feed if fitted.
- Check heating pipe joints, valves and air vents; repair leaks immediately.
- Check combustion air and ventilation to the boiler and mechanical room.
- Test the high limits by lowering settings and cycling the burner.
- Test the low water cut-off and check per the manufacturer's instructions; flush float types.
- Check lubrication of field-installed circulating pumps per manufacturer.
- On oil: check fuel lines are tight; clean or replace fuel filters annually; inspect the oil tank.
- On gas: check gas piping, unions, gas valve and manifold for gas tightness.
- Check ignition and operation of the oil or gas burner.
- Perform a combustion test.
- Check the door safety switch and the low water cut-off.
- Inspect the low and/or high pressure gas switch if fitted.
- Inspect the main burner flame and follow the burner maker's service instructions.
- Keep the boiler room free of dust, humidity, aggressive vapours and chlorine chemicals.
- Retighten or reseal the combustion chamber door, clean-out covers, fiber rope seals and flanges as needed.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200 VD2 Series 320 to 1080 Service Instructions, p. 15. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.