Viessmann Boiler: Actuator test
Actuator test on a Viessmann boiler: Each actuator can be switched on separately to check it. Before an actuator is selected, all actuators are switched off. Tests run at the relay outputs and depend on system equipment level and control unit configuration. Mixing valve tests need the supply temperature to rise when the valve opens.
Applies to: Actuator test of pumps, mixing valves, relays and solar outputs
Common causes of actuator test
- Supply temperature falls when the valve opens: motor turning in the wrong direction or valve set fitted incorrectly
How to fix actuator test: step by step
- From the home screen tap Menu, then Service.
- Enter the viservice password.
- Tap Actuator test.
- Select the actuator to test, for example DHW tank primary pump, DHW circ pump, Htg circ pump HC2 or HC3, Mixing valve HC2 or HC3, central fault message, EA1 output 1, AM1 output 1 or 2, or solar circuit pump.
- Confirm the actuator switches ON or moves to Open/Close.
- For a mixing valve, confirm the supply temperature rises on opening; if it drops, check motor rotation and valve installation against the mixing valve instructions.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
2.53.04.05.06.0CA3B 2.5CA3B 3.0CA3B 3.5CA3B 4.0CA3B 5.0CA3B 6.0CA3B Dual Fuel 2.5CA3B Dual Fuel 2.5 BoilerCA3B Dual Fuel 3.0CA3B Dual Fuel 3.0 BoilerCA3B Dual Fuel 3.5CA3B Dual Fuel 3.5 BoilerCA3B Dual Fuel 4.0CA3B Dual Fuel 4.0 BoilerCA3B Dual Fuel 5.0CA3B Dual Fuel 5.0 BoilerCA3B Dual Fuel 6.0CA3B Dual Fuel 6.0 BoilerCA3B Dual Fuel Series 2.5CA3B Dual Fuel Series 3.0CA3B Dual Fuel Series 3.5CA3B Dual Fuel Series 4.0CA3B Dual Fuel Series 5.0CA3B Dual Fuel Series 6.0Vitocrossal 300 CA3B Dual Fuel 2.5Vitocrossal 300 CA3B Dual Fuel 3.0Vitocrossal 300 CA3B Dual Fuel 3.5Vitocrossal 300 CA3B Dual Fuel 4.0Vitocrossal 300 CA3B Dual Fuel 5.0Vitocrossal 300 CA3B Dual Fuel 6.0Vitocrossal 300 CA3B Dual Fuel Series 2.5Vitocrossal 300 CA3B Dual Fuel Series 3.0Vitocrossal 300 CA3B Dual Fuel Series 3.5Vitocrossal 300 CA3B Dual Fuel Series 4.0Vitocrossal 300 CA3B Dual Fuel Series 5.0Vitocrossal 300 CA3B Dual Fuel Series 6.0
Source: Vitocrossal 300 CA3B Dual Fuel Service Instructions, p. 118. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.