Viessmann Air Handler: Refrigerant line installation limits
Refrigerant line installation limits on a Viessmann air handler: Basic line limits between the indoor and outdoor units.
Applies to: DLFUAA ductless system refrigerant lines
How to fix refrigerant line installation limits: step by step
- Use R410A only. Outdoor units ship with a full charge; line sizing is based on runs up to 25 ft (7.6 m).
- Keep the minimum line length between indoor and outdoor units at 10 ft (3 m).
- For runs over 25 ft, check the product data and add refrigerant up to the allowed length.
- Insulate the suction line with at least 1/2 in (12.7 mm) thick insulation. Closed-cell is recommended on long lines.
- If line is buried, do not bury more than 36 in (914 mm). Provide at least a 6 in (152 mm) vertical rise to the service valves.
- Isolate the tubing from the building structure so vibration and noise are not transmitted.
If the unit shows an error code, look it up: Viessmann Air Handler codes
Models
DLFLABH36XA3DLFLABH48XA3DLFLABH60XA3DLFSABH18XB3DLFSABH24XB3DLFSABH30XB3DLFSABH36XB3DLFUAAQ18XB3DLFUAAQ24XB3DLFUAAQ30XB3DLFUAAQ36XA3DLFUAAQ36XB3DLFUAAQ48XA3DLFUAAQ60XA3
Source: DLFUAA service manual, p. 12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.