Viessmann Air Handler: Electrical parts removal (control box and boards)
Electrical parts removal (control box and boards) on a Viessmann air handler: Disassembly of the electrical control box, main control board, data transfer board and transformer. Anti-static gloves must be worn.
Applies to: DLFUAA indoor air handler (Vitocal IND-A)
How to fix electrical parts removal (control box and boards): step by step
- Turn off all power before starting.
- Remove the 2 screws of the upper cover plate assembly, then remove the cover.
- Remove 2 screws, then unplug the plugs.
- Pull out the electric control box subassembly.
- Remove the 2 screws and the 1 ground screw.
- Unplug the plugs, then remove the main control board subassembly.
- Release the data transfer module control board screw (1) and remove the board.
- Release the 2 screws, then remove the transformer.
If the unit shows an error code, look it up: Viessmann Air Handler codes
Models
DLFLABH36XA3DLFLABH48XA3DLFLABH60XA3DLFSABH18XB3DLFSABH24XB3DLFSABH30XB3DLFSABH36XB3DLFUAAQ18XB3DLFUAAQ24XB3DLFUAAQ30XB3DLFUAAQ36XA3DLFUAAQ36XB3DLFUAAQ48XA3DLFUAAQ60XA3
Source: DLFUAA service manual, p. 35-36. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.