Trane Heat Pump: BK output wiring with variable speed indoor unit
BK output wiring with variable speed indoor unit on a Trane heat pump: The BK output sends a PWM airflow signal to a variable speed indoor unit. It needs the factory BK jumper removed at the indoor unit and the R-to-BK jumper cut at the control.
Applies to: BK output enabled systems
How to fix bk output wiring with variable speed indoor unit: step by step
- Cut or remove the R-to-BK jumper at the control.
- Set the indoor unit dip switches 5 and 6 to OFF.
- Leave the Y terminals on the indoor unit disconnected.
- Add a BK wire from the control to the variable speed indoor unit.
If the unit shows an error code, look it up: Trane Heat Pump codes
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 15. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.