Trane General: XR724 shows the wrong room temperature
XR724 shows the wrong room temperature on a Trane general: Room temperature on the XR724 does not match a good thermometer.
Applies to: Trane XR724 touchscreen comfort control TCONT724AS42DA (also sold under American Standard)
Common causes of xr724 shows the wrong room temperature
- Sensor needs a calibration offset
- Control was powered up less than an hour ago and is still warming up
- Heat from the touchscreen trapped in the case
- Supply air, sun, a lamp or another heat source hitting the control
How to fix xr724 shows the wrong room temperature: step by step
- After any power cycle, wait at least 1 hour before you judge or calibrate the reading.
- Look for drafts or heat sources near the control (supply register, sun, TV, lamp, outside wall). Move the control or redirect the air if needed.
- Calibrate the indoor sensor: Menu > Calibrate Sensors > Sensor Cal. Range is +/- 7 degrees, default 0 (1 degree F = 2 degrees C on this setting).
- If a remote or outdoor sensor is used, those have their own offset (Remote Sensor Cal, ODT Sensor Cal), same +/- 7 range.
If the unit shows an error code, look it up: Trane General codes
Source: Trane XR724 Comfort Control (TCONT724AS42DA) User Guide and Installer's Guide 18-HD82D1-1E-EN, Troubleshooting p.38 and Calibrate Sensors p.5. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.