Trane General: XR724 shows the wrong humidity
XR724 shows the wrong humidity on a Trane general: Indoor RH on the XR724 does not match a known good hygrometer.
Applies to: Trane XR724 touchscreen comfort control TCONT724AS42DA (also sold under American Standard)
Common causes of xr724 shows the wrong humidity
- Humidity sensor needs a calibration offset
How to fix xr724 shows the wrong humidity: step by step
- Compare with a hygrometer you trust, placed next to the control for a while.
- Set the offset in Menu > Calibrate Sensors > RH Cal. Range is +/- 7 %, default 0 %.
- Remember the humidifier / dehumidify and overshoot functions work from this reading, so fix it before you adjust humidity targets.
If the unit shows an error code, look it up: Trane General codes
Source: Trane XR724 Comfort Control (TCONT724AS42DA) User Guide and Installer's Guide 18-HD82D1-1E-EN, Troubleshooting p.38 and Calibrate Sensors p.5. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.