Trane General: XR724 fan set to On but blower not running
XR724 fan set to On but blower not running on a Trane general: Fan mode is On but the blower stays off.
Applies to: Trane XR724 touchscreen comfort control TCONT724AS42DA (also sold under American Standard)
Common causes of xr724 fan set to on but blower not running
- Smart Continuous Fan (SCF) is on and indoor RH is above the cooling RH target, so the control stops the fan to avoid putting moisture back in the air (SCF shows on the fan mode button)
- Equipment problem
How to fix xr724 fan set to on but blower not running: step by step
- Look for SCF on the fan mode button. If it is there and RH is high, this is normal.
- If the customer wants the fan running, turn SCF off or raise the cooling RH target.
- No SCF: run Test Mode > Blower. If the blower still does not start, check the indoor unit.
If the unit shows an error code, look it up: Trane General codes
Source: Trane XR724 Comfort Control (TCONT724AS42DA) User Guide and Installer's Guide 18-HD82D1-1E-EN, Troubleshooting p.38. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.