Trane General: No heat, XR724 not calling
No heat, XR724 not calling on a Trane general: The XR724 does not start heating. Check the control settings and timers first, then the equipment.
Applies to: Trane XR724 touchscreen comfort control TCONT724AS42DA (also sold under American Standard)
Common causes of no heat, xr724 not calling
- System mode not on Heat or Auto, or heat setpoint set too low
- Heating delta On set too high
- Minimum off time still counting down
- Problem in the heating equipment itself
How to fix no heat, xr724 not calling: step by step
- Check the mode is Heat or Auto (or EM Heat on a heat pump) and the setpoint is above room temperature.
- Check the heating delta On setting.
- Wait out the minimum off time. If it bothers the customer, change Control Response in Installer Settings > Comfort Settings.
- Use Menu > Test Mode > Indoor Heating (energizes W1 or W2, plus G on electric heat) or Comp Heating (Y1 or Y2 with G, BK on VS indoor units). Test Mode stays on for 30 minutes.
- Equipment does not run in Test Mode: check the wiring and the furnace / heat pump. Gas appliances: gas-qualified tech only.
If the unit shows an error code, look it up: Trane General codes
Source: Trane XR724 Comfort Control (TCONT724AS42DA) User Guide and Installer's Guide 18-HD82D1-1E-EN, Troubleshooting p.38 and Test Mode p.8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.