Trane Air Handler: Run test mode (furnace)

Updated · by Aurora Star Tech Inc.

Run test mode (furnace) on a Trane air handler: Lets the technician watch the blower perform its stages without starting the outdoor unit. Option holds (HLD) a step. The blower takes roughly 70 seconds to start the test.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: P0V0 modular blower integrated control (IMBC)

How to fix run test mode (furnace): step by step

  1. Press Menu until run appears, then press Option; the display flashes three times and the test begins
  2. Blower runs at 1st-stage compressor speed 30 s, then 2nd-stage speed 30 s; the pair repeats two more times
  3. Exit with a short press of Menu, by cycling blower power, or by making a valid call for capacity or fan
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Trane Air Handler codes

Models

P0V0A000M30SCAP0V0B000M40SCAP0V0C000M50SCAP0V0D000M50SCA

Source: Trane P0V0 modular blower installer's guide 18-GE20D1-1E-EN, Integrated Modular Blower Control Menu, p.29-30. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.