Change boiler water temperature

Viessmann · Single-boiler systems

Single-boiler systems only. In a multi-boiler system the tr button has no function and the current boiler temperature stays on the display.

  1. Press the tr button. The previous boiler water temperature setting flashes.
  2. Press the up/down button until the required temperature shows.
  3. Confirm with the confirm button (its symbol is not legible in the extract). The value stops flashing and is stored.

Change calorific value or correction factor

Viessmann · Energy cockpit

Changes the calculated gas consumption data. The consumption value is not suitable for billing purposes. Not valid for systems with a DHW tank with a temperature switch (such as an Aquastat).

  1. Open Settings, then 'Energy cockpit'.
  2. Select 'Calorific value' or 'Correction factor'.
  3. Enter the value.
  4. Confirm.

Change display language

Viessmann · Vitotronic 300-K and Vitotronic 200

The display may start in German at commissioning. The language is changed through the extended menu.

  1. Open the extended menu.
  2. Select Settings, then Language.
  3. Pick the required language with the selector.
  4. Press OK to accept.

Change domestic hot water temperature

Viessmann · Single-boiler systems with DHW tank

Not available in multi-boiler systems, where the Vitotronic 100 cannot control a DHW tank.

  1. Press the DHW button. The previous DHW temperature setting flashes.
  2. Press the up/down button until the required temperature shows.
  3. Confirm with the confirm button. The value stops flashing and is stored.

Change heating curve slope and level (extended menu)

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

Changes the heating curve to suit the system. Use the extended menu.

  1. Enter the extended menu.
  2. Select 'Heating' and press OK.
  3. Select the heating circuit and accept with OK.
  4. Select 'Heating curve' and press OK.
  5. Select 'Slope or level' and press OK.
  6. Change the value with the control dial.
  7. Select the heating curve that matches the system requirements.
  8. Exit.

Change heating curve slope and shift (extended menu)

Viessmann · Vitodens 222-F B2TB

Adjusts the heating curve slope or shift for a heating circuit in the extended menu.

  1. Open the extended menu.
  2. Select Heating, then press OK.
  3. Select the heating circuit.
  4. Accept with OK.
  5. Select Heating curve and press OK.
  6. Select Slope or Shift and press OK.
  7. Change the value with the arrow keys.
  8. Select the heating curve that matches the system requirements.
  9. Exit the menu.

Change heating curve slope or level (extended menu)

Viessmann · Vitodens 200-W B2HA 45, 60

Use the extended menu to change the slope or level of the heating curve so it matches the system.

  1. Open the extended menu.
  2. Select Heating, then press OK.
  3. Select the heating circuit and accept with OK.
  4. Select Heating curve, then press OK.
  5. Select Slope or Level, press OK.
  6. Change the value with the arrow keys and select the curve that fits the system.
  7. Exit the menu.

Change measuring units

Viessmann · Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Switches the display between metric and imperial units.

  1. From the home screen, open Menu, then Settings.
  2. Open Measuring units.
  3. Select Metric or Imperial.
  4. Tap OK to confirm.

Change room temperature and heating program from standard menu

Viessmann · Vitodens 200-W B2HA 80 to 100 and 285 to 352

Room temperature and heating program can be changed from the standard menu. Heating programs are standby with frost protection, DHW only, and heating and DHW.

  1. Use the arrow keys to set the required room temperature, then press OK.
  2. Select the required heating program with the arrow keys, then press OK.
  3. Wait 2 minutes or exit to return to the standard menu automatically.

Change room temperature and heating program from the standard menu

Viessmann · Vitodens 222-F, B2TB 19, 35, 68, 125

Room temperature and the heating program are set from the standard menu. Changes are confirmed with OK.

  1. Press the keys to set the room temperature to the required value, then press OK.
  2. Press the keys to select the required heating program, then press OK.
  3. Heating program options: standby with frost protection monitoring, DHW only, or heating and DHW.

Change room temperature or heating program in the standard menu

Viessmann · Programming unit standard menu

The standard menu covers the most-used settings for the heating circuit shown in the header.

  1. Press the keys shown in the manual (not legible in extract) to set room temperature, then press OK to confirm.
  2. Select a heating program: 9 standby with frost protection, w DHW only, or wz heating and DHW.
  3. Press OK to confirm.
  4. The display returns to the standard menu about 2 minutes after the last change.

Change room temperature set-point

Viessmann · Vitodens 222-F B2TB with Vitotronic control

Changes the standard room temperature set-point for a heating circuit using the control unit menu.

  1. Open the heating menu (step 1 icon not legible on the page).
  2. Select Heating.
  3. Select the heating circuit.
  4. Press OK.
  5. Select room temperature set-point and press OK.
  6. Change the value with the arrow keys.
  7. Accept with OK.
  8. Exit the menu.

Change room temperature setback

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

Set the reduced (setback) room temperature. Example in the manual: 41 F to 57 F (5 C to 14 C).

  1. Open the heating menu (button symbols in step 1 and 8 are not legible in the extracted text).
  2. Select 'Heating'.
  3. Select the heating circuit.
  4. Press OK.
  5. Select 'Red. room temperature setpoint' and press OK.
  6. Change the value with the control dial.
  7. Accept with OK.
  8. Exit the menu.

Change room temperature setpoint

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

Set the comfort room temperature for the heating circuit from the standard menu. Examples in the manual: 68 F to 79 F (20 C to 26 C).

  1. Open the heating menu (button symbols in step 1 and 8 are not legible in the extracted text).
  2. Select 'Heating'.
  3. Select the heating circuit.
  4. Press OK.
  5. Select 'Room temperature setpoint' and press OK.
  6. Change the value with the control dial.
  7. Accept with OK.
  8. Exit the menu.

Change standard room temperature setpoint and setback

Viessmann · Vitodens 200-W B2HB

Examples in the manual: setpoint 68F to 79F (20C to 26C); setback 41F to 57F (5C to 14C).

  1. Select Heating from the standard menu.
  2. Select the heating circuit and press OK.
  3. Select room temperature setpoint (or the setback setpoint) and press OK.
  4. Change the value and accept with OK.

Change temperature unit

Viessmann · Vitotronic 200

Factory setting is °C.

  1. Open the extended menu and select "Settings", then "Temperature unit".
  2. Select °C or °F.

Change temperature unit between °C and °F

Viessmann · Vitotronic 100 GC1B and Vitotronic 300-K MW1B

Factory setting is °C on both controls. Vitotronic 100 uses the key sequence shown on the display; Vitotronic 300-K uses the extended menu.

  1. Vitotronic 300-K: open the extended menu, select Settings, then Temperature unit.
  2. Vitotronic 300-K: select °C or °F.
  3. Vitotronic 100: press the settings key until its symbol flashes.
  4. Vitotronic 100: press the selector key until the temperature unit symbol flashes, then press OK.
  5. Vitotronic 100: choose °C or °F with the selector key, then press OK to save.

Change the adjustable high limit (maximum boiler water temperature)

Viessmann · Vitotronic 100 KW10B

The adjustable high limit caps the boiler water temperature on a call for heat. The default range is 104 to 167 °F (40 to 75 °C). The contractor can raise the range to 104 to 212 °F (40 to 100 °C).

  1. Choose the boiler water temperature the heating contractor recommends.
  2. Turn the selector clockwise to raise the limit.
  3. Turn the selector counter-clockwise to lower the limit.

Change the boiler (burner) sequence from the control panel

Viessmann · Cascade boilers controlled by the Vitocrossal 300 control unit

Boiler lead order is changed from the main menu, not a coding address.

  1. Tap Menu.
  2. Tap Boiler sequence.
  3. Select the required boiler sequence (burner sequence).
  4. Confirm with OK.

Change the boiler sequence (burner sequence)

Viessmann · Cascade control unit

Select the boiler sequence from the control unit menu. Button names are not legible in this extract.

  1. Tap the menu buttons shown on the control unit (page image not legible).
  2. Open the "Boiler sequence" entry.
  3. Select the required boiler sequence (burner sequence).
  4. Confirm the selection.

Change the default value shown on the scan key

Viessmann · Vitotrol 300 remote control, factory default display

Choose which value appears first when the scan key is pressed. Options include outside, supply, boiler water, DHW, return water and room temperature, flue gas temperature, time and date, where the sensor is installed.

  1. Press the scan key. The outside temperature is shown.
  2. Use the up/down keys to select the value.
  3. Confirm the selection.

Change the DHW temperature

Viessmann · Desired DHW temperature

In a multi-boiler system the Vitotronic 100 GC1 has no function for DHW temperature, so it is set on the Vitocontrol-S.

  1. Open the hinged cover on the programming unit.
  2. Press the DHW temperature button; the current setting flashes.
  3. Adjust the value with the up or down button.
  4. Confirm; the value stops flashing and is stored.
  5. Close the hinged cover.

Change the DHW temperature setpoint

Viessmann · Vitotrol 300 remote control, DHW temperature setpoint

Set the domestic hot water temperature at the remote control. The temperature value flashes while you edit it.

  1. Open the flip-down cover of the remote control.
  2. Select the DHW temperature. The value flashes.
  3. Use the up/down keys to enter the desired temperature.
  4. Confirm. The value stops flashing and is saved.
  5. Close the flip-down cover.

Change the display language

Viessmann · Vitotrol 300 remote control

English is the factory language. Change it from the outside temperature screen.

  1. Open the flip-down cover of the remote control.
  2. Scroll until the outside temperature screen appears.
  3. Press the key until the wanted language shows.
  4. Confirm; the display returns to the time.
  5. Close the flip-down cover.

Change the display language (Vitotronic 300-K)

Viessmann · Vitotronic 300-K MW1B

Selects the language used on the control display.

  1. Open the extended menu.
  2. Select Settings, then Language.
  3. Select the required language.

Change the heating curve slope and level

Viessmann · Vitodens 200-W B2HB heating circuits

Changed in the extended menu to match the heating system requirements.

  1. Open the extended menu.
  2. Select Heating, then press OK.
  3. Select the heating circuit.
  4. Accept with OK.
  5. Select Heating curve, then press OK.
  6. Select Slope or Level, then press OK.
  7. Change the value with the arrow keys.
  8. Select the heating curve that suits the system requirements.
  9. Exit the menu.

Change the heating curve slope and shift

Viessmann · Vitodens 200-W B2HB heating circuits

Done from the extended menu under the heating circuit selection.

  1. Call up the extended menu.
  2. Select Heating, press OK, then select the heating circuit.
  3. Accept with OK, then select Heating curve and press OK.
  4. Select Slope or Shift and press OK, change the value, and select the curve matching the system.
  5. Exit the menu.

Change the normal (day) room temperature

Viessmann · Vitotronic 300 Model GW2

Sets the room temperature used during the normal heating periods. Factory setting is 20°C / 68°F, active from 06:00 to 22:00. Adjustable from 3 to 37°C (37 to 99°F).

  1. Press the heating circuit selector button so it lights up.
  2. Turn the ts selector knob to the required temperature.
  3. Wait a moment; the display returns to showing the boiler temperature.

Change the normal room temperature

Viessmann · Vitotrol 300 remote control

Normal room temperature is adjustable from 50 to 86 °F (10 to 30 °C). Default is 68 °F / 20 °C from 06:00 to 22:00.

  1. Open the flip-down cover of the remote control.
  2. Press the normal room temperature key; the display shows the setting.
  3. Use the up/down keys to choose the temperature.
  4. Press to confirm; the temperature stops flashing and is saved.
  5. Close the cover.

Change the operating mode from the standard display

Viessmann · Versatronik 200 System Control, operating mode

The operating mode can be changed quickly from the standard display. Party and Reducing functions can also be set with the function keys, with the rotary knob setting the length of the increase or interruption.

  1. From the standard display, press the function button under the operating mode line.
  2. Turn the rotary knob to select the mode.
  3. Press OK to save, or End to leave without saving.
  4. For Party or Reducing, press the matching function button and set the duration with the rotary knob.
  5. Turn the knob left to apply Party or Reducing for whole days, for example Reduced 5 Days.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.