Other: Water Heater tips (part 3 of 3)
Short, practical technician tips on other for water heater. Check each one against the manual for your exact model before acting.
Freeze protection for the tank
Viessmann · Vitocell 100-V CVWC
The tank must sit in a frost-protected, draft-free room. If that cannot be guaranteed, drain the tank whenever it is not in use.
- Confirm the mechanical room never sees freezing temperatures.
- Drain the tank if it is out of use and freezing is possible.
Heat coil temperature limit during welding or brazing
Viessmann · Vitocell 100-V CVWC
The heating coil uses a rubber seal and glue inside the tank, so it cannot take high heat. Do not let the NPT fitting area exceed 302°F (150°C) during welding or brazing.
- Keep the NPT fitting area at or below 302°F (150°C) during any welding or brazing.
- Use caution around the coil seal and glue when doing hot work near the tank.
Heat exchanger self-venting and self-draining
Viessmann · Vitocell 100-V CVWC, all sizes
The tubular coil is self-venting at the top and self-draining at the bottom, so air lock or deposits should not cut heat transfer. The coil reaches the bottom of the tank so the whole water volume is heated.
Heat transfer medium requirements
Viessmann · Vitocell 100-V CVWC
The heat coil medium must be potable water or substances FDA-recognized as safe. It must also be non-toxic with a toxicity class of 1. Keep its pressure below the minimum operating pressure of the potable water system, and limit it to a maximum of 30 psig with an approved safety or relief valve.
- Use potable water or an FDA-safe, non-toxic fluid in the heating circuit.
- Keep the heat transfer medium pressure below the domestic water minimum operating pressure.
- Limit the heat transfer medium to 30 psig maximum with an approved safety or relief valve.
Intended use limits
Viessmann · Vitocell 100-V CVWC
The tank is for sealed unvented systems and stores only potable water. It is not for steam heating. Do not use it for commercial or industrial purposes beyond building heat or DHW without manufacturer approval. Do not modify components, for example direct DHW heating in the collector.
- Confirm the system is sealed and unvented.
- Do not install the tank in a steam heating system.
- Do not modify the tank or its connections for uses outside the intended design.
Not for steam heating
Viessmann · Vitocell 100-V CVWC, all sizes
This tank version must not be used on steam heating systems.
Recirculation tapping
Viessmann · Vitocell 100-V CVWC
The recirculation connection is on its own tapping. Cap it if the tank is installed without a recirculation line.
- Cap the recirculation tapping if no recirculation line is installed.
Scald risk from hot domestic water
Viessmann · Vitocell 100-V CVWC
DHW above 125°F (52°C) can cause severe burns almost instantly or death from scalds, and children, disabled and elderly people are most at risk. Temperature limiting valves must be used wherever the storage tank temperature can exceed 140°F (60°C). Advise the owner to feel the water before bathing or showering.
- Install temperature limiting valves or a tempering valve where the tank can exceed 140°F (60°C).
- Tell the owner to test water temperature before bathing or showering.
Seal unused connections
Viessmann · All Vitocell 100-V CVWC sizes
The protective covers are not watertight, so unused connections must be sealed during installation.
- Seal every unused connection on the tank before filling or pressurizing the system.
Standard equipment on each CVWC tank
Viessmann · Vitocell 100-V CVWC 200 L, 250 L and 300 L
Every CVWC tank ships with the same standard kit: a welded sensor well for the tank temperature sensor or controller, a temperature and pressure relief valve, installation fittings, a technical literature set, adjustable feet and factory insulation. The casing is epoxy-coated sheet steel in Vitopearl white.
Standard equipment, Vitocell 100-V CVWC 53, 66 and 79 USG
Viessmann · Vitocell 100-V CVWC 53, 66 and 79 USG
Each size ships with a steel DHW tank with enamel coating, an integral welded sensor well for the tank temperature sensor or controller, a temperature and pressure relief valve, installation fittings, a technical literature set, adjustable feet and fitted insulation. Casing is epoxy-coated sheet steel in Vitopearlwhite.
Start one-off DHW heating
Viessmann · One-off DHW heating
Heats the DHW tank once to the set DHW temperature, outside the time program. This has higher priority than the time program. It ends when the target temperature is reached.
- Call up the home screen.
- Select DHW, then confirm with OK.
- Select One-off heating, then confirm with OK.
- Select to activate, then confirm with OK.
- Acknowledge the information with OK.
Switch on the DHW hygiene program
Viessmann · DHW hygiene program
Heats the DHW tank above 140°F (60°C) once a week, or for an hour every day, at the set time. Scald risk: mix with cold water at draw-off points. Not valid for systems with a DHW tank thermostat (Aquastat-type).
- Call up the home screen.
- Select DHW, then confirm with OK.
- Select Time program, then confirm with OK.
- Select DHW, then confirm with OK.
- Select DHW, then confirm with OK.
- Select Hygiene program, then confirm with OK.
- Select the required day or everyday, then confirm with OK.
- Select the required hour, then confirm with OK.
- Select the required minutes, then confirm twice with OK.
- Press and hold the exit button for about 4 sec to leave the menu.
Tank layout: anode, clean-out port and DCW diffuser
Viessmann · Vitocell 100-V CVWC, all sizes
The tank has an impressed current anode, an enamel-lined steel shell with foam-in-place insulation, and an inspection and clean-out port. The cold water diffuser is positioned with the coil so 82 to 97 percent of tank volume can be drawn at constant temperature.
Water quality and chloride/sulfate limits
Viessmann · Vitocell 100-V CVWC
The tank must heat drinking (potable) water only. Chloride and sulfate levels are limited. In areas with high levels, consult Viessmann before installing. Water treatment equipment must work correctly. Heating other media voids the warranty.
- Confirm the water is drinking quality.
- Check chloride and sulfate levels against the limits.
- Consult Viessmann if levels are high.
AQUA PLUS water heater piping rules
Weil-McLain · Ultra boilers with AQUA PLUS water heaters
AQUA PLUS indirect water heaters need a diaphragm or bladder expansion tank and an automatic air vent. Connect the water heater loop per the AQUA PLUS manual.
- Use a diaphragm or bladder expansion tank with AQUA PLUS water heaters. Do not use a closed-type tank.
- Install the DHW relief valve in the top tapping of the AQUA PLUS water heater.
- Keep the water heater loop within 12 in. apart at the primary/secondary tees where shown.
- With DHW as priority 1, the U-Control turns off space heating during DHW heating. The boiler circulator stops, unless a timeout setting overrides it.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.