Other: Heat Pump tips (part 3 of 5)
Short, practical technician tips on other for heat pump. Check each one against the manual for your exact model before acting.
Antifreeze selection and handover when filling with glycol
Viessmann · Filling and antifreeze protection
Only use antifreeze made for hot water heating systems. Automotive silicate-based antifreeze must not be used. Inform the owner that the system contains a glycol mix and provide the antifreeze Safety Data Sheet.
- Confirm the antifreeze is made for hot water heating systems and is not automotive silicate-based.
- Keep glycol at or below 50% in the system water.
- Check pH and the system frequently after filling with antifreeze.
- Give the system owner the antifreeze Safety Data Sheet and tell them the system contains glycol.
Built-in protection and diagnostics
Viessmann · DLCURA outdoor units
The unit includes controls and safeties that protect the outdoor fan, compressor and system.
- Check the time delay control sequence run by the fan coil board when the unit restarts.
- Check outdoor fan motor protection if the fan does not run.
- Use the system diagnostics when a fault is suspected.
- Check compressor motor current and temperature overload protection if the compressor trips.
Built-in protection features on heat pumps
Viessmann · Heat pump indoor units
Indoor units include freeze protection and high coil temperature protection in heating mode. Cold blow protection and freeze protection mode are also standard.
Built-in protection functions
Viessmann · All D5CSRA outdoor units
The factory-set minimum protections are: time delay control sequence through the fan control board, compressor discharge over-temperature, system low voltage, compressor overload, compressor over-current, outdoor fan failure, and system diagnostics.
Capacitors stay charged after power off
Viessmann · Outdoor unit
Electricity remains in the capacitors after the power supply is off. Fully discharge them before troubleshooting the outdoor PCB or IPM.
- Discharge the capacitors fully before any troubleshooting on the outdoor PCB or IPM.
Check capacitor discharge before troubleshooting or board work
Viessmann · DLCSRB indoor and outdoor PCBs
Capacitors keep a charge after the power is off. Confirm they are discharged before working on the boards.
- Turn off all power supplies or disconnect all wires.
- Measure the voltage between P and N on the back of the main PCB with a multimeter.
- If the reading is below 36 V, the capacitors are fully discharged.
- Wear anti-static gloves or a wrist strap when handling the indoor or outdoor PCB.
Cleaning the unit
Viessmann · Vitocal 100-WA
Use only approved cleaning methods. Commercial and special heat exchanger cleaners can damage the heat pump.
- Clean the unit surfaces with a damp cloth only.
- Clean the air coil shutters with a long bristle brush.
- Brush the air coil only from top to bottom or bottom to top, never side to side.
Compressor and back-up heater indicators
Viessmann · Vitocal 100-AW AM2V indoor unit display
A solid compressor symbol means the compressor is running. A flashing compressor symbol means the compressor is running and outdoor temperature is low enough for electric heating element activation. The electric heating element symbol shows when it is active, and the back-up heating symbol shows when back-up heating is on.
- Check the compressor symbol on the display to confirm compressor operation.
- Check the back-up heating and electric element symbols when the unit is in low outdoor temperature.
Condensate drain in cold climates
Viessmann · DLCURA outdoor unit
In cold climates, keep the drain hose as vertical as possible so water drains quickly. Slow drainage can freeze in the hose and flood the unit.
- Connect the drain joint with an extension hose so condensate does not drip off during heating mode.
- Check the drain hose slope and direction before leaving the site.
Defrost parameter guidance for heavy snow areas
Viessmann · Vitocal 100-AW AM2V outdoor unit defrost
Standard defrost settings may not be enough in heavy snowfall. Raising S12 and S13 and lowering S14 can help.
- Increase S12 (defrost duration) and S13 (defrost water entering temperature).
- Decrease S14 (defrost interval).
Display symbols on the operating screen
Viessmann · Vitocal 100-AW AM2V controller display
Symbols show the running program (schedule, disinfection, defrost, party, holiday, frost protection, manual), heat take-up for central heating or hot tap water, cooling operation, error and warning, electric heating element active, compressor running (flashing means bivalent mode) and back-up heating on.
- Check the symbols on the home screen to confirm the active program and heat source.
- A flashing compressor symbol means bivalent mode is active.
Do not leak test with air or oxygen-containing gas
Viessmann · Refrigerant system leak testing
Pressurized air or gas mixtures containing oxygen can explode. Use dry nitrogen or another inert gas for leak testing and never for operating compressors.
- Do not use air or oxygen-containing gas for pressure or leak testing.
- Use an approved inert gas for leak testing.
Drain heating water before removing refrigerant
Viessmann · Vitocal 100-WA
Hydronic components can freeze when refrigerant is removed.
- Drain the heating water from the heat pump before refrigerant is removed.
- After the refrigerant work, vent the hydronic system properly and make sure the area is well ventilated, since refrigerant may have entered the water side.
Electrical entry points and DHW pump switch
Viessmann · Vitocal 100-WA
Each corner post has two openings for routing wiring. Knockouts in the junction box provide cable restraints. The DHW desuperheater pump switch is at the top of the junction box. The unit has outputs for a closed-loop source pump and an open-loop source valve.
- If DHW is not connected to this unit, set the desuperheater DHW pump switch to OFF.
Electrical installation rules
Viessmann · All models
The control must be grounded. L1, L2 and G must not be swapped. Size all wire to the local electrical code. Each circuit needs its own disconnect near the unit. A licensed electrician must do line voltage work; the certified contractor may do only Class 2 low voltage wiring such as the thermostat.
- Ground the control.
- Confirm L1, L2 and G are wired correctly and not interchanged.
- Size wire per NEC/CEC or local code.
- Provide a separate disconnect for the circuit near the unit.
Electrical shock hazard before service
Viessmann · DLCLRC
Main disconnect must be off before installing, modifying or servicing the system.
- Switch off the main electrical disconnect. There may be more than one disconnect.
- Lock out and tag the switch with a suitable warning label.
Errors and warnings on the home screen
Viessmann · Vitocal 100-AW AM2V indoor unit
When an error or warning is present, the home screen shows an error indicator or a warning indicator. The list of detected errors and warnings is opened from the navigation dial. Error code values are not listed on these pages.
- Press the navigation dial to open the list of detected errors and warnings.
- Record the codes shown and check the fault tables in the full manual.
Fibreglass and ceramic fibre handling
Viessmann · Installation and service work with insulation materials
Fibreglass wool and ceramic fibre materials are a possible cancer hazard by inhalation.
- Avoid breathing dust and contact with skin and eyes.
- Wear a NIOSH-approved dust/mist respirator, long-sleeved clothing, gloves and eye protection.
- Wash work clothes separately and rinse the washer well.
- Rinse eyes with water to remove dust; wash skin with soap and cool water.
- Move anyone with respiratory irritation to a dust-free area.
Field wiring safety checks
Viessmann · All D5CSRA systems
Every wire must be firmly connected, since loose wiring can overheat terminals, cause malfunction or create a fire hazard. No wire may touch refrigerant tubing, the compressor or moving parts. A disconnect must be provided within sight of the air conditioner and be readily accessible. Follow local code when running wire from the indoor to the outdoor unit.
- Tighten every wire connection.
- Route wires so none touch tubing, the compressor or moving parts.
- Install a disconnect within sight of the unit and easy to reach.
- Follow local code for the indoor-to-outdoor run.
Field wiring workmanship
Viessmann · DLCLRC sizes 36K-58K
Loose connections can overheat terminals, cause malfunction and create a fire hazard. Wires must not touch refrigerant tubing, the compressor or moving parts. A disconnecting means must be within sight of and readily accessible from the air conditioner. Route the connecting cable through the hole in the conduit panel.
- Tighten every field wire connection firmly.
- Keep all wires clear of refrigerant lines, compressor and moving parts.
- Install a disconnect within sight of the unit.
- Run the connecting cable through the conduit panel hole.
Filter and construction dust
Viessmann · All ducted installs
Use a high-efficiency air filter in tight buildings and tell the owner it needs regular changes, usually monthly. Do not run the unit during construction or remodeling, as dust can clog the coil and condensate drain and will void the warranty.
- Install a high-efficiency filter.
- Tell the owner the filter schedule.
- Do not run the system during construction or remodeling.
Filter and panel removal
Viessmann · Indoor unit filter and panel
Removal method depends on whether the panel has a lift function.
- If the panel has a lift function, grab the air grille with your fingers and pull it out slowly.
- If the panel has no lift function, push one side of the grille clamp on both sides of the grille.
- Remove the 2 screws, then remove the grille.
Flammable R32 refrigerant: ignition control before work
Viessmann · Vitocal 100-AW AM2V outdoor unit (R32)
The outdoor unit uses flammable R32. A leak can form a flammable or explosive mix with air, so keep ignition sources away from the work area.
- Keep flames, hot surfaces, non-certified electrical devices and battery-powered devices away from the work area.
- Use only tools rated for A2L/A3 refrigerants, such as brushless tools, non-sparking mechanical tools and suitable vacuum pumps.
- Touch earthed metal such as heating or water pipes to discharge static before starting.
- Do not use sprays or other flammable materials.
- Post no-smoking signs and have a CO2 or dry powder extinguisher at hand when draining, topping up or doing hot work.
FOLLOW ME function
Viessmann · DLFSOAH09XAK, DLFSOAH18XAK
When active, the unit controls to the room temperature sent by the remote and ignores its own room sensor. The function ends automatically if no remote signal arrives for 7 minutes, or when FOLLOW ME is pressed again.
- Press FOLLOW ME on the wireless or wired remote to start it.
- Press FOLLOW ME again to stop it.
Freeze protection during refrigerant work
Viessmann · Vitocal 100-AW AM2V hydronic circuit
Hydronic parts can freeze when refrigerant is removed, and frost protection needs power.
- Drain the heating water from the heat pump before removing refrigerant.
- Thermally insulate all hydronic lines.
- Connect the heat pump electrically and switch on the power before filling the secondary circuit, so frost protection works.
Freeze stat lockout
Viessmann · Open loop heating mode
The freeze stat protects the liquid-to-refrigerant heat exchanger. In heating mode it reads refrigerant temperature leaving the water coil. If that drops below the freeze set point, the system activates freeze protection and locks out until manually reset.
- Check water flow and groundwater temperature if the freeze stat trips.
- Correct the cause before resetting.
- Reset the lockout manually.
Frequent defrost cycles
Viessmann · Outdoor unit sizes 18K to 60K
If the outdoor unit defrosts often, the thermal balance point can be adjusted to reduce cycling and cold air during defrost.
- Adjust the thermal balance point to a temperature that reduces defrost recurrence.
- The thermal balance point is the outdoor ambient temperature at which the heat pump can no longer provide enough heat alone without compromising compressor reliability.
Heat pump operating principle
Viessmann · Vitocal 100-AW AM2V
The outdoor unit holds the whole refrigerant circuit with an inverter-driven compressor and an electronic expansion valve. The indoor unit holds the controller, secondary pump, electric auxiliary heater and a 3-way diverter valve for space heating or DHW. In cooling mode the refrigerant circuit reverses.
Hot and cold surfaces and fluids
Viessmann · Vitocal 100-AW AM2V
Hot heating water and cold refrigerant surfaces can cause scalds, burns or frostbite.
- Switch off the equipment and let it cool down or warm up before servicing.
- Do not touch hot or cold surfaces on the appliance, fittings or pipework.
- If water leaks, isolate the heating system at the external isolator before touching anything, and never touch hot heating water.
How to read the DLCURA cooling and heating performance tables
Viessmann · DLCURA 18K HH and 24K outdoor units (cooling and heating performance)
Cooling tables are split by airflow (CFM). Each block lists outdoor dry bulb temperature down the side. Across the top are indoor wet bulb groups (60.8, 64.4, 66.2, 71.6 F) and, under each, indoor dry bulb values (73.4, 77.0, 80.6, 84.2 F). TC is total cooling capacity in BTU/hr, S/T is sensible-to-total ratio, and PI is total power input in kW. Heating tables list TC (total capacity, BTU/hr) and PI (total power, kW) against indoor dry bulb (60.8, 68.0, 71.6, 75.2 F) for each airflow block. Gray shaded cells are extrapolated data, not tested points.
- Pick the airflow block that matches the indoor blower CFM.
- Find the outdoor dry bulb row, then the indoor wet bulb and dry bulb column.
- Read TC for capacity, S/T for the sensible share, and PI for power draw.
- Treat gray shaded values as estimates only.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.