Other: Boiler tips (part 4 of 45)
Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.
Wiring a low water cutoff (LWCO) switch
Navien · NCB700 low water cutoff wiring
The boiler supplies 24 VAC to the LWCO power terminals (CNC3). For line-voltage LWCO switches, the manual shows a typical method where the burner and control circuits share the same voltage, using a jumper between the switch terminals.
- Connect the LWCO switch power to the 24 VAC terminals (CNC3) on the boiler board.
- For a line-voltage switch, use the typical wiring with a jumper as shown in the manual.
- Confirm the wiring matches the diagram before power-up.
3-way valve motor must be disconnected for heating-only use on TRX150 / TRX199
NTI · TRX150 and TRX199 models, heating-only installs
If the boiler only serves heating and is not connected to an indirect water heater, the 3-way valve motor must be disconnected while the boiler runs in central heating mode. This locks the valve in CH so freeze protection works. Leaving the valve connected can disable freeze protection and cause property damage.
- Confirm the boiler is heating only, with no indirect water heater.
- Disconnect electrical power before working on the wiring.
- Disconnect the 3-way valve motor so it stays locked in central heating mode.
Antifreeze selection
NTI · TRX150
Only use antifreeze made for hydronic systems that contains propylene glycol. Never use automotive or standard ethylene glycol antifreeze, which attacks seals and is toxic. Check the antifreeze is compatible with the stainless steel heat exchanger.
- Use propylene glycol antifreeze made for hydronic systems.
- Use the mix and quantities the antifreeze maker gives for your region.
- Do not use automotive or ethylene glycol antifreeze.
Auto Boost behaviour
NTI · NTI TRX boilers, outdoor reset
Auto Boost (4.7.5 = 1) raises the outdoor reset slope by 10 percent every 10 minutes while a call for heat stays on, up to 2 times the nominal slope (4.2.2). When the call is satisfied, the slope drops 1 percent per minute back to the nominal value. Only works when 4.2.1 = 3 or 4.
Canada vent installation requirements
NTI · Canadian installations
Extra requirements for Canadian installations.
- Use a vent system certified to ULC-S636.
- Keep the first 3 ft of vent pipe from the flue outlet readily accessible for inspection.
- Do not mix components with other vent systems or unlisted pipe or fittings.
- Keep plastic vent and boiler parts at least 8 in from high heat sources (100 F / 37 C or greater).
Carbon monoxide detector placement
NTI · All installations
Required CO detector placement in the home.
- On each floor with bedrooms, place a CO detector and alarm in the living area outside the bedrooms.
- Also place one in the room that houses the boiler.
- Use detectors that comply with NFPA 720 (latest edition).
Ceramic fiber dust in the combustion chamber
NTI · TRX150
Combustion chamber insulation contains ceramic fiber that can form cristobalite at high temperature. Limit dust exposure.
- Wet the combustion chamber lining before disturbing it to prevent dust.
- Wear an N95 NIOSH certified respirator, long sleeves, gloves and eye protection.
- Wash contaminated clothing separately and rinse the washer.
- If dust reaches the eyes, irrigate immediately. If breathing is affected, move to fresh air.
Condensate float switch
NTI · TRX boilers
The condensate collection system has a float switch that monitors condensate level and prevents backup into the boiler.
Control panel buttons and display layout
NTI · TRX150 control panel
Front panel has ON/OFF, DHW +/- (item 2), MENU (item 3), HISTORY (item 4), RESET (item 5), OK (item 6), ESC (item 7), CH +/- (item 8) and the display (item 9). The ON/OFF button lights white when the boiler has power and stays dark during an error or power failure. The RESET button lights red on a lockout. A short MENU press opens the user menu and a long MENU press opens the info menu.
- Press ON/OFF to power the boiler on or off.
- Press MENU briefly for the user menu.
- Press and hold MENU for the info menu.
- Use the CH +/- or DHW +/- buttons to change setpoints from the home screen.
Day and night room setpoints
NTI · NTI TRX boilers with room sensor
Daily comfort setpoint factory 70 F, night reduced setpoint factory 61 F. Only applies with NTI room sensor. Zones 1 and 2 can have different setpoints, applied with the selected mode and time program. Allowed target ranges depend on each other as shown in the setpoint graph.
Display icons and what they mean
NTI · TRX150 control panel
The display shows boiler status, temperature in °F with a bar level, error codes with the word ERROR, a RESET request on lockout, and menu settings. Icons show: technical assistance request, flame with power level, CH heating set or active, DHW set or active, hot water comfort (combi only), antifreeze active (boiler off or on), AUTO outdoor reset control, error signal, outdoor sensor connected (optional) and WiFi active.
- If the error icon is lit, read the code and description on the display.
- If the RESET request appears, press RESET after the cause is fixed.
- If the technical assistance icon shows, call for service.
Do not add cold make-up water to a hot boiler
NTI · TRX boilers, system fill and service
Adding cold water to a hot boiler causes thermal shock that can crack the heat exchanger. This damage is not covered by warranty. Also, continual fresh make-up water shortens boiler life and must be stopped by repairing leaks at once.
- Let the boiler cool before adding make-up water.
- Repair leaks in the boiler or piping right away.
Do not adjust excess flow valve screws without analyzer
NTI · NTI TRX150 gas valve
Screws 2 (offset) and 4 (throttle) on the gas valve must not be removed or adjusted without a calibrated combustion analyzer. Doing so can cause fire, property damage or serious injury.
- Leave the EFV offset and throttle screws alone unless a calibrated combustion analyzer is connected.
Do not use solvents or operate with missing parts
NTI · TRX150
Solvents can damage boiler components. Missing condensate trap parts make the boiler unsafe to run.
- Clean boiler components with water or approved solution only.
- If any condensate trap part is missing, do not run the boiler. Replace the whole trap assembly.
Exhaust vent slope, support and terminations
NTI · Exhaust vent and intake installation
Support the vent so it does not carry its own weight on the boiler connections, and keep it draining back to the boiler.
- Pitch the exhaust vent at least 1/4 inch per foot back toward the boiler so condensate drains.
- Do not use vent connections to support the piping.
- Insert the supplied exhaust and intake screens into both terminations to stop debris and birds getting in.
- Pipe exhaust and intake separately. Do not share a common exhaust or intake with other appliances.
Freeze protection is off when the boiler has no power
NTI · TRX boilers
The control's freeze protection does not work if power is lost. Plan piping and location with freeze risk in mind. Freeze damage is not covered by warranty.
Glycol limits for DHW and IWH loops
NTI · TRX boilers with glycol
Use only food grade propylene glycol rated GRAS for indirect water heater loops. Glycol content must not exceed 50% unless the manufacturer says otherwise. Non-GRAS glycol is only allowed in closed loop CH applications. Check glycol periodically so it does not turn acidic. Never use automotive or standard ethylene glycol.
- Use food grade propylene glycol (GRAS) for IWH loops.
- Keep glycol at or below 50% of the liquid.
- Test glycol periodically for acidity.
Massachusetts venting requirements
NTI · Massachusetts and local code installations
Signage and piping labels required in Massachusetts and where state or local codes require them.
- Do not take combustion or dilution air from a bedroom or bathroom.
- Where a through-the-wall vent is less than 7 ft above grade, mount a metal or plastic sign at least 8 ft above grade in line with the vent.
- Sign text must read 'GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS' with letters at least 0.5 in high.
- Label exposed piping every 10 ft and concealed piping every 3 ft, at all direction changes, and on both sides of any wall or ceiling penetration.
- Labels must be black lettering at least the pipe diameter in height, up to 2 in maximum.
Overheat cutoff and lockout at 212°F
NTI · TRX boilers
The temperature controls are UL 353 listed. They shut off the fuel when the set point is reached. At 212°F, the boiler goes into safety shutdown and lockout and needs a manual reset.
Scald risk at DHW temperatures
NTI · NTI TRX150 DHW installations
Water above 125 F can cause severe burns or death. Children, disabled and elderly people are at highest risk. An ASSE 1017 or ASSE 1070 temperature limiting or mixing valve is recommended where those users are present. Mixing valves do not remove the scald risk entirely.
- Set the water heater setpoint as low as practical.
- Install a temperature limiting or mixing valve where disabled, elderly or children are served.
- Advise users to feel the water before bathing or showering.
Scalding water when draining
NTI · TRX150
Water drained from the boiler can be very hot.
- Let the boiler cool before draining.
- Take precautions when draining water.
Service clearances and combustible spacing
NTI · TRX boilers, indoor install only
Clearance to combustibles is 0 inches on top, bottom, sides and back. Minimum service clearance is 18 inches front, 14 inches top, 12 inches bottom, 2 inches each side and 0 inches back. A combustible door or removable panel is acceptable at the front, with at least 3 inches from the front cover. Keep 8 inches from high heat sources.
Set date and time manually
NTI · NTI TRX boilers with 365-day clock
Date and time must be correct for time programs to work. If the boiler is on the Wi-Fi app, the Internet time is used automatically. Manual entry only appears when ITIME is OFF.
- Make sure ITIME is set to OFF in the user menu.
- Set day (1-31), month (1-12), year and time.
- Use the hour and minute buttons shown in Figure 57 (items 2 and 8).
- Press OK to confirm the entered data.
Summer/winter changeover operation
NTI · NTI TRX boilers with user menu 11 and 12 set
With automatic changeover on, the boiler switches from winter to summer mode based on outdoor temperature. Factory switchover temperature is 68 F. If outdoor temperature stays more than 1 F above the switchover temperature for 5 h, the boiler goes to summer mode. If it stays more than 1 F below for 5 h, it returns to winter mode. In summer mode the boiler can turn heating off.
Use the correct gas diaphragm and mixer for the fuel
NTI · TRX150
Install the gas diaphragm and mixer that match natural gas or propane. Propane needs the mixer from the conversion kit.
- Check the fuel type before fitting the mixer or diaphragm.
- For propane, install the mixer from the natural gas to propane conversion kit and the gas diaphragm required for propane.
- Follow the conversion kit instructions.
Vent insulation and material rules near the boiler
NTI · Exhaust vent routing and insulation
Some insulation and pipe materials are not allowed close to the boiler because they can overheat and fail.
- Do not insulate the first 3 linear feet of exhaust vent.
- Do not insulate PVC, CPVC or polypropylene exhaust pipe.
- Use CPVC, polypropylene or stainless steel for the first 3 linear feet if that run passes through an enclosed space longer than 6 inches, such as a wall or ceiling.
- If you use CPVC or polypropylene or stainless steel for that run, use the same material for the rest of the vent run, except CPVC can be followed by PVC.
- Do not insulate non-metallic vent pipe or fittings.
- Keep at least 8 inches from high heat sources at 100°F or more, such as flue pipes or space heaters.
- Only stainless steel exhaust pipe may be insulated, and a double-wall vent can be used in freezing climates.
Venting material and adapter rules
NTI · Exhaust and intake material compatibility
Mixing materials without the right adapters can let flue gas leak into the living space.
- Never use B vent for exhaust. It is for intake only.
- Do not use PVC in the closet or alcove in the US or Canada. Use approved CPVC, polypropylene or stainless steel.
- When venting with PVC, insert the factory supplied 5 inch length of CPVC into the boiler exhaust connection before transitioning to PVC. Do not insert PVC directly into the boiler exhaust connection.
- For AL29-4C stainless vent, fit a PVC-to-stainless adapter at the boiler vent connection and at the termination when a PVC termination kit is used.
- Do not mix AL29-4C from different manufacturers unless the manufacturer's adapters are used.
- Do not use cellular core PVC, cellular core CPVC or Radel.
- Do not remove the factory-installed exhaust and intake components near the appliance, or the warranty is void.
Wiring safety: label wires and keep 120 V away from control wiring
NTI · TRX150
Wiring mistakes can cause unsafe operation. Label every wire before disconnecting, and keep 120 V cables separate from low voltage control cables.
- Label all wires before disconnecting them when servicing.
- Do not connect 120 V to any control wiring terminal.
- Use separate cables for 120 V and low voltage control circuits.
Boiler that was under water
Rinnai · All I-Series Plus models
Do not use the boiler if any part has been under water. A licensed professional must inspect it and replace any control system part and any manual gas control valve that was under water.
- Do not run the boiler.
- Have a licensed professional inspect the boiler.
- Replace the control system parts and manual gas control valve that were under water.
Do not install in restricted or unsafe areas
Rinnai · I-Series Plus condensing combi boiler
Keep the boiler out of areas where it can be damaged or where airflow is restricted.
- Do not install where leakage would damage the area or lower floors. If that cannot be avoided, install a drained drain pan that does not block combustion air.
- Do not install under negative air pressure.
- Do not block combustion or ventilation air.
- Do not install on carpeting.
- Do not install outdoors.
- Do not use parts that are not authorized for this boiler.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.