Other: Boiler tips (part 25 of 45)
Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.
Never run the boiler without venting
Viessmann · Vitocrossal 200 CI2
Carbon monoxide from a missing or faulty vent can poison occupants.
- Do not operate the boiler unless the venting system is installed.
- Confirm all combustion products vent safely to the outdoors.
- Check the venting section of the manual for venting and chimney requirements.
No batteries in the programming unit
Viessmann · Vitotrol 200A
The remote control is powered by the control unit. Do not insert batteries into the programming unit.
No frost protection when aBA is used as a safety switch-off
Viessmann · Vitotronic 300 GW6B
Switch-off through the aBA terminals stops the boiler and leaves the system without frost protection.
- Use the aBA terminals for safety switch-off only, for example through a high limit thermostat.
- Warn the owner that the heating system is not frost protected while the boiler is blocked.
No user serviceable parts
Viessmann · Vitotronic 100 KW10B
There are no user serviceable parts on the boiler, burner or control. Only a licensed professional heating contractor may install, adjust, service or maintain the equipment.
No user-serviceable parts
Viessmann · Vitocrossal 300 CA3B
The end user must not perform service work on the boiler, burners or controls.
- Only a qualified heating contractor should service the boiler, burners or control.
- Owner checks only as listed in the service schedule.
Non-Viessmann DHW tank and tempering valve
Viessmann · Vitocrossal 300 CU3A DHW systems
Requirements for a DHW tank that is not a Viessmann tank.
- If the DHW tank is not a Viessmann Vitocell 100 or 300, verify the DHW tank temperature sensor with the tank manufacturer.
- Install a temperature tempering valve in the DHW supply line, as Viessmann strongly recommends.
Non-Viessmann DHW tank applications
Viessmann · Vitodens 200-W B2HA 45, 60
Non-Viessmann tanks need extra checks for sensor operation and coil flow.
- Verify the Viessmann DHW sensor works with the original tank manufacturer.
- Install a temperature tempering valve in the DHW supply line.
- Size the DHW coil pressure drop against the field pump residual head to keep flow to the boiler heat exchanger.
- Keep DHW piping between boiler and tank connections at least 1¼ in.; undersized piping can cause short-cycling and poor DHW supply.
Non-Viessmann DHW tank requirements
Viessmann · Vitodens 200-W B2HB with non-Viessmann DHW tanks
If a DHW tank other than a Viessmann Vitocell 100 or 300 is used, the installer must confirm the Viessmann DHW tank sensor works correctly with the tank manufacturer. Viessmann strongly recommends a temperature tempering valve in the DHW supply line.
- Verify the Viessmann DHW tank sensor with the original tank manufacturer.
- Install a temperature tempering valve in the DHW supply line.
Not a safety control and no user-serviceable parts
Viessmann · Versatronik COMO OT room controller
The room controller is not a safety control. Only licensed or qualified heating contractors should install, adjust, service or maintain it. There are no user-serviceable parts inside.
Nozzles that must be installed by the installer
Viessmann · Riello direct vent burners
For VR1 27, 105 with Riello direct vent, the installed nozzle must be replaced with the nozzle packaged with the burner. The 0.60x60°W nozzle is installer-installed. For VR1 33, 140 the 0.85x60°W nozzle is factory installed.
Offline boiler timeout and zero values
Viessmann · Versatronik 585 VI/BACIP
If a boiler sends no data for 10 minutes, the gateway treats it as offline and reports zero for all its points. This applies to LON communication only, not KMK.
- If a boiler reports 0 degrees for boiler water temperature, the gateway skips all other points for that boiler.
- Check that boiler is connected and powered if it reports zeros for all its points.
Oil appliance draft requirement
Viessmann · VR1 22 to 33, 91 to 140
Oil-fired appliances must always connect to vents with enough draft for safe, proper operation.
Oil burner start-up safety checks
Viessmann · All VR1 models
Warnings to follow before lighting the burner.
- Do not use gasoline, crankcase drainings or any oil containing gasoline.
- Do not start the burner unless the combustion chamber door is secured in place.
- Do not attempt to start the burner when excess oil has accumulated, the unit is full of vapor, or the combustion chamber is very hot.
- Do not fire the boiler without water.
- Do not leave tools inside the combustion chamber.
- Never burn garbage or paper in the unit.
Oil pump set-up for single-line or two-line fuel supply
Viessmann · Oil pump on the burner
The burner ships set for single-line operation with no oil pump changes needed. For two-line systems, the bypass plug must be installed.
- Leave the oil pump as shipped for single-line systems.
- For a two-line system, install the bypass plug in the oil pump.
On-board Vitotronic 200 controls and tools
Viessmann · Vitotronic 200 HO1B
The HO1B control is built into the boiler. The standard unit has the ON/OFF switch, Optolink interface, operating and fault indicators, reset button and fuses. The programming unit has the display and keys and can be wall mounted with an accessory.
- Use the programming unit display and keys to set room temp, DHW temp, heating programs, time programs, economy and party modes, holiday program, heating curves, codes, actuator tests and test mode.
- Use the Optolink port for laptop access.
- Use the reset button on the standard unit for resets.
- Check fuses on the standard unit when troubleshooting power.
One function per connection
Viessmann · Vitodens 200-W B2HA 19, 28, 35
Each connection on the wiring diagram can carry only one function or accessory.
- Assign only one function or accessory to each connection.
One-off DHW heating outside the time program
Viessmann · Domestic hot water
Starts domestic water heating for a single period outside the programmed phases.
- Press the DHW button twice, 2 to 3 seconds apart.
Open the main menu from any screen
Viessmann · Vitotronic 300-K cascade control programming unit
The main menu holds the boiler sequence, all cascade settings such as heating defaults and time programs, and the scanning functions.
- If the screensaver is active, tap the screen and then tap Menu.
- From any menu level, tap the menu button in the footer and then tap Menu.
Open the Vitotronic 200 KW6B control
Viessmann · Vitotronic 200 KW6B
Access the control and power it up for start-up.
- Lift the programming unit to the upright position.
- Adjust the angle with the side push button if needed.
- Open the control cover.
- Switch the on/off switch to on.
Opening the control
Viessmann · Vitotronic 100 KW10B
The control cover is opened from the front and the top cover is unlocked with a screwdriver.
- Open the front cover.
- Carefully unlock the control top cover with a screwdriver.
- Flip the top cover open to reach the control PCB.
Opening the control unit
Viessmann · Vitotronic 100 GC1
Access the inside of the Vitotronic 100 control unit.
- Remove the cover of the connection enclosure.
- Unscrew the screws from the front housing.
- Swing up the front part of the control housing.
- Position the stay bar so it supports the front housing.
Opening the Vitotronic control unit
Viessmann · Vitotronic 100 and Vitocontrol-S control units
Procedure to open the control unit housing for service access.
- Remove the cover of the connection enclosure.
- Unscrew the screws from the front housing.
- Swing up the front part of the control housing.
- Position the stay bar so it supports the front housing.
Operating modes for central heating
Viessmann · Vitodens 100-W B1HE and B1KE
The contractor sets one of two modes during commissioning. In weather-compensated operation, supply water temperature follows outside temperature, so colder days get higher supply temperature. In constant operation, the boiler holds a fixed supply temperature regardless of outside temperature.
- Confirm with the contractor which mode the system uses before changing heating settings.
Operating modes set by the installer
Viessmann · Vitodens 100-W B1HE/B1KE
The control unit runs in weather-compensated or constant operation. The heating contractor sets the mode during commissioning.
- Weather-compensated: supply water temperature follows outside temperature, so colder weather gives a higher supply temperature.
- Constant: the boiler holds a fixed supply water temperature regardless of outside temperature.
- Confirm the configured mode with the commissioning record before changing settings.
Operating program choices
Viessmann · Operating program setting
The operating program sets what the system heats. Options are central heating with DHW, DHW only with no central heating, or frost protection only for the boiler and DHW tank with no central heating and no DHW. There is no operating program for central heating without DHW, because central heating normally runs together with DHW in winter mode.
Operating program options
Viessmann · Vitotronic 300 GW6C control
The operating program defines whether the boiler heats the central heating and DHW, only DHW, or only provides frost protection. No program provides central heating without DHW.
- Select central heating and DHW for winter operation.
- Select DHW only for summer operation to keep DHW running with central heating off.
- Select frost protection only to keep the boiler and DHW tank protected with no heating or DHW.
Operating program selection
Viessmann · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0
Choose DHW only (central heating off, DHW still heated, summer use) or Heating and DHW.
- Go to Menu > Heating > required heating circuit > Operating program.
- Select DHW only or Heating and DHW.
- Press OK to confirm.
- In DHW only, frost protection for the boiler and DHW tank stays enabled. Standby mode also keeps frost protection active.
Operating program selection for summer and standby
Viessmann · Vitocrossal 300 CA3B, all sizes 2.5 to 6.0
Use DHW only mode in warm months, or standby mode when neither heat nor hot water is needed for long periods.
- Select the DHW only operating program to keep hot water on with central heating off.
- Select standby mode when heating and DHW are not needed for long periods.
Operating programs for DHW and standby
Viessmann · Vitocrossal 300 CA3B Dual Fuel
Summer mode uses the DHW only program, so the boiler heats domestic hot water but not the central heating. Standby mode is for long periods without heat or hot water needs. Holiday program lowers room temperature and turns off DHW.
- Select DHW only for summer hot water with no heating.
- Select Standby mode for long periods with no heating or hot water.
- Select the holiday program when away to reduce room temperature and turn off DHW.
Operating status: standard and reduced heating
Viessmann · Vitotrol 300A
In the Heating and DHW program the operating status switches between standard and reduced heating mode.
- Standard heating mode: rooms are heated to the standard room temperature during the times set in the central heating time program.
- Reduced heating mode (setback): rooms are heated to the reduced room temperature when out or at night, during the times set in the central heating time program.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.