Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Other: Boiler tips (part 22 of 45)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.

Keep combustion air free of contaminants

Viessmann · Vitodens 100-W B1HE/B1KE

Contaminated combustion air damages the boiler and can cause property damage or injury. Chemicals such as chlorine, halogenated solvents and dust are common causes.

  1. Check the installation area for contaminant sources such as pool chemicals, refrigerant leaks, cleaners, dust or new construction.
  2. Do not install the boiler in areas with chemical exposure.
  3. Do not close existing ventilation openings.
  4. Avoid continuous high humidity in the boiler room.

Keep combustion and ventilation air clean

Viessmann · Vitocrossal 200 CI2

Contaminated combustion air can damage the boiler and cause serious hazards.

  1. Do not store chemicals, garbage, gasoline, flammable vapours or liquids near the boiler, even temporarily.
  2. Do not close existing ventilation openings.
  3. Avoid continuously high humidity in the boiler room.
  4. Check that nothing blocks combustion and ventilation air flow.

Keep combustion and ventilation air open

Viessmann · Vitocrossal 300 CA3B Dual Fuel

Closed or blocked fresh air openings in the mechanical room cause incomplete combustion and poisonous gases.

  1. Make sure combustion air openings and ventilation air openings in the mechanical room are open.
  2. Do not close or obstruct these openings.
  3. Keep the boiler and boiler room free of combustible materials, gasoline and flammable vapors.

Keep gateway wiring away from 120/240 VAC conductors

Viessmann · Versatronik 505 and 505D

Wires run near high-voltage conductors can pick up electromagnetic interference. Avoid this where possible. If it cannot be avoided, use stranded twisted-pair or shielded wire, and ground only one end of the shield.

  1. Route low-voltage wiring away from 120/240 VAC conductors.
  2. If close routing is unavoidable, use stranded twisted-pair or shielded cable.
  3. Ground only one end of the shield.

Keep leak spray away from electrical contacts

Viessmann · Gas valve

Leak detection spray can cause a malfunction if it reaches electrical contacts.

  1. Keep leak detection spray off electric contacts when leak testing the gas valve.

Keep LON and low-voltage wiring away from mains wiring

Viessmann · All Versatronik 501 and 501D gateways

Long wire runs can pick up electromagnetic interference. Keep the LON wiring clear of 120/240 VAC conductors. If that cannot be done, use stranded twisted-pair shielded wire and ground only one end of the shield.

  1. Route LON wiring away from 120/240 VAC conductors.
  2. If the runs must be close, use stranded twisted-pair shielded wire.
  3. Ground only one end of the shield.

Keep LON wiring away from line voltage

Viessmann · LON field wiring

Long wire runs can pick up electromagnetic interference.

  1. Do not run LON wires beside or near 120/240VAC conductors.
  2. If you cannot avoid them, use stranded, twisted-pair shielded wire.
  3. Ground only one end of the shield.

Keep safety labels in place

Viessmann · Vitodens 200-W B2HB 19 to 35, 68 to 125

Follow the safety instructions on boiler labels and stickers. Do not remove them. Contact Viessmann if a replacement label is needed.

  1. Check that all labels and stickers on the boiler surfaces are present and legible.
  2. Order replacement labels from Viessmann if any are missing or damaged.

Keep standard room temperature at or below 68°F (20°C)

Viessmann · Vitocrossal 300 CU3A

Every degree of room temperature reduction saves up to 6% on heating bills. Use the time program to set reduced temperatures at night.

  1. Set the standard room temperature no higher than 68°F (20°C).
  2. Set a time program so the home is at standard temperature in the day and reduced temperature at night.

Keep the boiler and boiler room clear

Viessmann · Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

The boiler must be kept clear of combustibles and flammable material, and combustion and ventilation air must not be blocked. The boiler must be cleaned at least once a year by a qualified heating technician or service agency.

  1. Keep the boiler and boiler room free of gasoline, flammable vapors and liquids, and combustible materials.
  2. Do not block combustion or ventilation air.
  3. Have a qualified heating technician clean the boiler at least once a year.

Keep the front cover on and check combustion air

Viessmann · Vitodens 222-F, B2TB 19, 35, 68, 125

Do not run the boiler without the front cover. Do not run it where combustion air is contaminated by dust, lint or chemicals, which can damage the boiler and cause serious harm.

  1. Keep the front cover in place whenever the boiler runs.
  2. Check the boiler room for dust, lint and chemicals before start-up.
  3. Have the boiler inspected and serviced by a qualified contractor at least once a year.

Keep the installation and service documents with the boiler

Viessmann · Vitotronic 300 KW3

The installation, operating and service instructions should go in the service document ring binder, which can be kept in an optional service box.

  1. File the installation, operating and service instructions in the service binder.
  2. Store the binder near the boiler where service personnel can reach it.

Keep vent termination above snow level

Viessmann · Sidewall and vertical vent terminations

Vent termination must sit well above the expected snow level so snow cannot block it.

  1. Check local snow level with building authorities or the local weather office.
  2. Set the termination at least 12 in above that level.
  3. Make sure snow cannot block the termination.

Label and check wiring during control service

Viessmann · Vitodens 200-W B2HA 19, 28, 35

Wiring errors can make the boiler run improperly and dangerously. Replacement wires must match the original exactly.

  1. Label all wires before disconnecting them when servicing controls.
  2. Replace any original supplied wire only with an exact equivalent.
  3. Verify proper operation after servicing.

Lag boiler faults are not sent to the BMS

Viessmann · GW6B cascade

The lead boiler reports when any lag boiler has a fault, but the gateway does not pass that to the BMS, so the lead does not appear faulted. The lag boiler's fault code is shown under its own boiler fault point. Boiler 1's fault point only shows faults from the lead boiler. If the physical control shows a fault that the gateway does not report, check the matching boiler fault point.

Lag boiler section service display location

Viessmann · Vitocrossal 300 CA3B multi-boiler installations

In a multi-boiler setup, service messages for lag sections B and C show on the lower panel and need the lower front panel and control cover opened. Service messages for section A on lag boilers use the top panel, depending on the fault.

  1. For section B or C service messages, open the lower front boiler panel and control cover.
  2. For section A on a second, third or fourth boiler, open the top front panel and control cover if the fault requires it.

Lago FB display indicators

Viessmann · Lago FB remote control

Burner stages I and II, heating operation (D, with Z meaning pump on), DHW operation (!, with Z meaning pump on), mixing valve open/closed (y/z), BUS communication OK, room temperature and time (C/F), holiday days remaining (HO), outside temperature (AF, with outside sensor), boiler temperature (H), heating circuit supply temperature (D), DHW tank temperature (!), and fault (E001).

Lago FB display status indicators

Viessmann · Lago FB remote with Versatronik 200

The Lago display shows status symbols for burner, heating, DHW, mixing valve, holiday mode, temperatures and faults. Use the value selector dial with the mode dial set to RUN to view current information.

Lambda Pro automatic gas adjustment

Viessmann · Gas type changes on Vitodens 200-W B2HB

Lambda Pro adjusts combustion to the gas type and quality automatically, so no fuel conversion kit is needed for natural gas or LPG.

  1. Do not fit a fuel conversion kit for natural gas or liquid propane.
  2. Check combustion with CO2 or O2 readings and compare to the air factor table.

Lambda Pro combustion management and self-calibration

Viessmann · Vitocrossal 300 CU3A 26 to 199

The control reads ionization current to set the air factor, then sets the gas valve to suit the gas quality. It self-calibrates after power failures and at burner start. Brief high CO can appear during calibration.

  1. Expect the automatic calibration to run for about 5 seconds shortly after burner start.
  2. Do not judge combustion readings during calibration. CO can briefly be higher than normal.

Lead and lag section layout in single and multi-boiler setups

Viessmann · Vitocrossal 300 CA3B

Single boiler sections are set up without opening any front panels. Section A is the lead, B is lag 1, and C is lag 2 on 5.0 and 6.0 models. Multi-boiler setups use the lag numbering in sequence.

  1. Single boiler: A is lead section 1, B is lag 1 (section 2), and C is lag 2 (section 3) on 5.0 and 6.0.
  2. Multi-boiler: all sections are controlled and displayed from the first boiler's lead control (section 1).
  3. Open the lower panel and control cover on the second, third or fourth boiler to set up lag control.

Lead cascade dynamic control strategy (lead boiler only)

Viessmann · Lead boiler in a cascade

Adjusts the dynamic control strategy and runtime optimization so each boiler in the cascade has the same runtime. Also sets which boiler starts first or last.

Leak test after gas work

Viessmann · Gas valve, burner tube, burner fan, burner door and electrode work

Gas leakage can cause an explosion. Always leak test any gas line or gas valve connection you have disconnected.

  1. Leak test the reconnected gas line and valve connections before leaving the boiler.
  2. Use only approved leak detection fluid for natural gas and propane.

LED2 communication indicator

Viessmann · Versatronik 502 / 502D gateway

LED2 blinks each time a Modbus request is seen on the network. If it never blinks, the master is not reaching the gateway.

Lifting the boiler

Viessmann · CA3B Dual Fuel 2.5 to 6.0

Use lifting equipment rated for at least the boiler weight. Do not lift by the flue gas collector.

  1. Use certified lifting devices rated to at least the full boiler weight.
  2. Lift with lift-truck forks at the side locations (centre the forks on the / mark) or at the front location.
  3. Do not lift the boiler at the flue gas collector; damage can cause flue leakage.
  4. Lift the boiler by crane only while it is still in its packaging.

Lightguide status light meaning

Viessmann · Vitocrossal 200 CI2 control unit

A red illuminated strip (Lightguide) sits at the lower or upper edge of the control unit depending on boiler type. Its behaviour shows the system state. Slow pulsing means standby. Steady light means someone is operating the control unit, and each input is confirmed by a short flash. Fast flashing means a fault is present. The Lightguide can be switched off in the Settings menu.

  1. If the Lightguide pulses slowly, the display is in standby. No action is needed.
  2. If the Lightguide is steady, the control unit is in use.
  3. If the Lightguide flashes quickly, a fault is present. Check the message lists in the main menu for the fault.

Lightguide status meanings

Viessmann · Vitodens 100-W B1HE and B1KE, control unit display

The red Lightguide strip on the control unit shows the system state. A slow pulse means standby. Constant light means the control unit is being operated, and each input gives a short flash. A quick flash means there is a fault in the system. No fault code is shown with this signal on these pages. The Lightguide can be switched off in the settings.

  1. If the Lightguide flashes quickly, check the active messages in the main menu for a fault.
  2. To turn the Lightguide off or on, use the Lightguide setting in the display menu.

Limit aquastat for underfloor heating

Viessmann · Vitotronic 200 KW2 heating circuit with underfloor heating

A field-supplied electromechanical limit aquastat protects underfloor heating and floor covering. It switches off the heating circuit pump when the preset temperature is exceeded.

  1. Set the aquastat within 59 to 203 ºF (15 to 95 ºC).
  2. Wire the aquastat to the heating circuit pump circuit as the diagram shows.

Limit aquastat wiring jumper

Viessmann · Power/pump module, high limit aquastat connection

A jumper is fitted across terminals L-L. It must be removed before the high limit aquastat is connected.

  1. Remove the jumper from terminals L-L.
  2. Connect the high limit aquastat (optional) to those terminals.

Literature to leave on site

Viessmann · Vitorond 100 installation

Keep the boiler literature at the installation site and tell the owner where it is stored. The set includes the Technical Data Manual, Installation Instructions, Service Instructions, Operating Instructions, instructions for other Viessmann products used, and Hydrostat 3250-Plus instructions.

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977