Other: Boiler tips (part 15 of 45)
Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.
Domestic hot water tank connection point
Viessmann · Vitotronic 300-K cascade systems with DHW tank
If a DHW tank is part of the system, connect it at the Vitotronic 300-K, not at the boiler control.
Domestic hot water temperature limit warning
Viessmann · Systems with DHW tank connected to the control
Check the DHW tank temperature cannot exceed its maximum permitted value when the control runs with a DHW tank. Add a suitable safety device if the tank cannot guarantee this.
Domestic hot water temperature warning
Viessmann · Systems with domestic hot water tank
If the system is used with a domestic hot water tank, make sure the maximum allowed DHW temperature is not exceeded. Install a suitable safety device if needed.
Domestic hot water temperature with high limit
Viessmann · Systems with a DHW tank and adjustable high limit
If the system is operated with a domestic hot water tank, do not exceed the maximum permissible DHW temperature. Install a suitable safety device if needed.
- Check that the maximum permissible DHW temperature is not exceeded.
- Install a suitable safety device if needed.
Domestic hot water via indirect cylinder
Viessmann · Vitocrossal 200 CM2 with indirect-fired storage tank
The boiler can supply domestic hot water through an indirect-fired storage tank. Connections and a correctly sized circulating pump are needed. The DHW control circuit is built into the Vitotronic control.
- Make the appropriate boiler connections to the storage tank.
- Fit a circulating pump of the correct size.
- Set up the DHW circuit in the Vitotronic control.
Draining the boiler at the end of heating season
Viessmann · Vitotron 100 VLN2
Do not drain water from the boiler after the heating season.
- Leave the water in the boiler at the end of the heating season.
EA1 extension terminal layout
Viessmann · EA1 extension
The EA1 extension has three digital inputs (DE1, DE2, DE3), a 0-10 V analog input, a mains connection, a power supply for extra accessories, a floating switching output (aBJ) and a KM-BUS connection.
EA1 internal extension terminals
Viessmann · Internal extension EA1
Extension EA1 has three digital inputs (DE1 to DE3), a 0-10 V input, power supply terminals and output aBJ (central fault message, feed pump or DHW recirculation pump, potential-free).
- Refer to the main wiring diagram on page 95 before wiring field contacts.
- Assign the function of each input and of output aBJ with the coding codes listed on the following pages.
Economy mode (energy saving)
Viessmann · Vitotronic 300-K
Lowers room temperature in standard heating mode, for example when the building is empty for a few hours.
- Open the extended menu and select Heating.
- Select the heating circuit if needed.
- Select Economy mode and set it as required.
- To end early, set Economy mode to OFF.
- It also ends automatically when the time program switches to reduced heating mode.
Electrical code compliance
Viessmann · Vitocrossal 300 CU3A electrical installation
Electrical installation must follow the current NEC (ANSI/NFPA 70) and any state or local codes in the USA. In Canada, follow the CEC (CSA C22.1 Part 1) and any provincial or local codes.
- Follow NEC / ANSI/NFPA 70 and local code in the USA.
- Follow CEC CSA C22.1 Part 1 and local code in Canada.
Electrical code requirements
Viessmann · Vitocrossal 300 CU3A 26 to 199
Wiring must follow the current national electrical code and local rules. In the US that is the NEC, and in Canada the CEC.
Electrical connection overview: wiring points on the boiler
Viessmann · CA3B Dual Fuel, all models
The connection overview lists where field wiring lands on the CA3B Dual Fuel boiler.
- Route sensor and low-voltage wiring in the lower cable tray.
- Route power supply wiring in the upper cable tray.
- Connect supply temperature sensors for heating circuits M2/M3, external LON participants (Vitotronic 200-H), pumps and mixing valve, the internal disconnect switch with lockout provision, the EA1 extension and the fuel selector switch.
- On 5.0 and 6.0 models, the Section 3 control is also wired in.
Electrical installation requirements
Viessmann · Vitodens 100-W B1HE/B1KE
The control must be grounded. L, N and G must not be interchanged. Installation must follow the NEC/ANSI/NFPA 70 in the USA or the CEC/CSA C22.1 Part 1 in Canada, plus local rules.
Electrical safety before servicing
Viessmann · Versatronik 200 System Control
The control has more than one live circuit. The control is not a safety device, and there are no user-serviceable parts inside.
- Turn off power to the control and to the damper/blower before servicing.
- Check the wiring diagram in the manual, because more than one circuit is live.
- Keep static electricity under control when working inside the control, since static-sensitive components can be damaged by improper handling.
Electrical service precautions
Viessmann · Vitocrossal 300 CU3A service
Safety notes for wiring and service work.
- Disconnect power before servicing the boiler.
- Label all wires before disconnecting them when servicing controls.
- Replace any original wire only with an exact equivalent.
- Verify proper operation after servicing.
Electrical servicing precautions
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199
WARNING: Disconnect power before servicing the boiler. Electrical installations must follow the NEC (ANSI/NFPA 70) and state or local codes in the U.S.A., or the CEC (CSA C22.1 Part 1) and provincial or local codes in Canada. Wiring errors can cause improper and dangerous operation.
- Disconnect power before servicing the boiler.
- Label all wires before disconnecting them.
- Replace any original wire only with an exact equivalent.
- Assign only one function or accessory to each connection.
- Verify proper operation after servicing.
Electrical supply and condensate drain location
Viessmann · Vitodens 222-F B2TB
The external accessories connection box needs a 120 VAC wall receptacle supply. The condensate drain is on the boiler side. See the wiring diagram on page 41 for connections.
- Run 120 VAC to the external accessories connection box.
- Connect the condensate drain on the side of the boiler.
Electrical use of zone circulators
Viessmann · Vitocrossal CU3A zoned systems
Zoning with several circulators adds electrical consumption. Check for more efficient options during design.
Electrical work code requirements
Viessmann · All Vitodens 200-W B2HB models
All field wiring must follow the latest National Electrical Code (US) or Canadian Electrical Code (Canada) plus any state, province or local rules.
Emergency and dangerous-condition shutdown
Viessmann · Versatronik 503 NR2/Analog Bridge
If a dangerous condition exists, shut the system down at once.
- Turn off main power immediately.
- Close the gas supply valve.
- In an emergency, switch off the external power supply to the panel at its separate fuse or power supply.
Enable separate room temperature sensor on remote control
Viessmann · Vitotrol 200 and Vitotrol 300
When a separate room temperature sensor is connected to the remote control, its DIP switch must be turned on.
- Open the top casing of the remote control to reach the printed circuit board DIP switches.
- For Vitotrol 200, set DIP switch S6.3 to ON.
- For Vitotrol 300, set DIP switch S30.3 to ON.
Energy metering correction factor and calorific value
Viessmann · Energy metering
Used to set the arithmetic consumption calculation. The numeric values are not printed on these pages.
- Select Energy metering, then Consumption, then Settings.
- Select Correction factor or Calorific value, then confirm with OK.
- Enter the values and acknowledge with OK.
Energy saving recommendations
Viessmann · Vitotrol 300A users
Reduce room and DHW temperatures and use the right program to save energy.
- Do not set the room temperature above 68 °F (20 °C); each degree of reduction saves up to 6% on heating costs.
- Do not set the DHW temperature too high.
- Enable the DHW recirculation pump only when DHW is drawn off.
- Use economy mode for short absences and the holiday program for longer absences.
- In summer, use the Only DHW program if rooms do not need heat.
- Use Standby mode if neither rooms nor DHW are needed for an extended period.
Energy saving settings
Viessmann · Vitocrossal 200 CI2 central heating and DHW
Lower the DHW temperature at night or during absences and limit DHW recirculation to the hours of use. Keep standard room temperature at or below 68°F (20°C). Use the reduced room or supply temperature at night and during absences. Set unused heating circuits to Standby mode, and use the holiday program when away, which lowers the room temperature and turns off DHW heating.
- Adjust the DHW time program and DHW recirculation time program to match hot water use.
- Set the room set temperature to 68°F (20°C) or less.
- Set Standby mode on heating circuits not needed (for example central heating in summer).
- Select the holiday program before going away.
Energy saving settings for the standard room temperature
Viessmann · Vitocrossal 300 CA3B, all sizes 2.5 to 6.0
Each degree of room temperature reduction saves up to 6% on heating. The standard room temperature should not exceed 68°F (20°C).
- Keep the standard room temperature at or below 68°F (20°C).
- Use the time program to heat to standard temperature during the day and reduced temperature at night.
- Use Economy mode for short absences.
Energy saving tips for DHW and heating
Viessmann · Vitodens 100-W B1HE and B1KE
Lowering the DHW temperature at night or during absences saves energy. Each degree of room temperature reduction saves up to 6% on heating bills. In weather-compensated operation, keep the standard room temperature at or below 68°F (20°C).
- Lower the DHW time program or temperature for nights and absences.
- Use DHW recirculation only during the times hot water is regularly used.
- In weather-compensated operation, keep the Standard temperature level at or below 68°F (20°C).
- Use a reduced room or supply temperature at night and during absences.
Energy saving tips for the heating system
Viessmann · Heating systems controlled with Vitotrol 300
Practical habits that reduce heating energy use. Heating contractor maintenance and insulation also matter.
- Ventilate properly and do not overheat.
- Aim for a room temperature of 20 ºC (68 ºF). Each degree saves up to 6 % of heating cost.
- Use reduced room temperature at set times.
- Keep radiators and thermostatic valves unobstructed and adjust valves properly.
- Adjust the DHW tank temperature at the control unit.
- Use hot water in a controlled way. A shower typically uses less energy than a bath.
- Have the heating system maintained regularly by the heating contractor.
- Check insulation of heating system and DHW piping, outside walls, roof, windows and between heated and unheated rooms.
Enter contractor contact details
Viessmann · Control panel
Contact details entered here can be called up later in the Information menu.
- Open Information.
- Select 'Contractor contact details'.
- Select the entry field.
- Enter the contractor's details in each box.
- Confirm.
Example single-boiler layout with three-way mixing valve
Viessmann · Single-boiler system with Therm-Control and three-way mixing valve, Vitorond 200 VD2A
Circuit diagram 1 shows a single Vitorond 200 VD2A boiler with Therm-Control and a three-way mixing valve. The diagram includes a heating circuit with mixing valve, a DHW tank with primary and circulation pumps, a burner with stage 2 or modulating output, and a 120 VAC supply that needs a main isolator. External connections are covered in the Vitotronic 300 GW2 control manual.
- Install the main isolator per local regulations before connecting the power supply.
- Use the Vitotronic 300 GW2 control manual for external connections.
Example: boiler set-point boost after switching to normal room temperature (FA:20, Fb:30)
Viessmann · Vitotronic 200-H, Model HK1M
When operation changes from reduced to normal room temperature, the boiler set-point is raised by a percentage for a set time. Example: boiler set-point from the heating curve is 50°C / 122°F; with FA 20% it becomes 60°C / 146°F and is held for 60 minutes (Fb 30 steps at 2 minutes each).
- Confirm FA (raise %) and Fb (duration) values in Coding 2.
- Note the boiler set-point from the heating curve at the time of the switch.
- Verify the raised set-point holds for the coded duration before it returns to the curve.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.