Other: Air Handler tips (part 6 of 6)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on other for air handler. Check each one against the manual for your exact model before acting.

Check capacitors are discharged before troubleshooting

Viessmann · Indoor and outdoor PCB service

Capacitors keep charge after power is off. Measure the voltage between P and N on the back of the outdoor main PCB. A reading below 36 V means the capacitors are fully discharged. Use anti-static gloves or a wrist strap when handling boards.

  1. Turn off all power and disconnect wires.
  2. Measure the voltage between P and N on the outdoor main PCB with a multimeter.
  3. Continue only if the reading is below 36 V.
  4. Wear anti-static gloves or a wrist strap when touching the indoor or outdoor PCBs.

Electric auxiliary heater power

Viessmann · DLFUAA with EHKMB auxiliary heat

The electric auxiliary heater needs its own power supply.

  1. Do not power the electric heater from the outdoor unit.
  2. Follow the EHKMB installation manual for the heater.
  3. Paste the auxiliary heat wiring diagram supplied with the accessories in its designated spot after installing the heat modules.

Field water level float switch (CN5)

Viessmann · Main board CN5 WATER LEVEL switch input

Input for a field-supplied float switch. Jumper J1 must be removed to enable it. Closed contacts mean normal. Open contacts mean overflow, which sends a signal to the system to shut the unit off.

  1. Remove jumper J1.
  2. Connect the field-supplied float switch to CN5.
  3. Confirm the contacts are closed during normal operation.

Network address for central controller

Viessmann · Micro-switch S1 and dial S2 network address

Micro-switch S1 and dial switch S2 set the network address when a central controller is used. The address range is 00 to 63. The factory setting figure is not legible in this copy, so check the address on the unit before changing it.

  1. Set the address with S1 and S2 in the 00 to 63 range.
  2. Record the address and confirm the central controller communicates with the unit.

Power feed and auxiliary heater circuit

Viessmann · DLFSAB / DLFLAB with electric auxiliary heater

Outdoor unit supplies main power to the indoor unit, so turning off the outdoor unit also removes indoor power. No indoor-side disconnect is needed on the link wiring; a 3-pole disconnect may be added for extra protection. The electric auxiliary heater needs its own branch circuit with a field-supplied disconnect within sight of and readily accessible from the unit. Do not connect it to the indoor unit breaker.

  1. Isolate the outdoor unit power when the indoor unit must be de-energised.
  2. Use a separate branch circuit with a disconnect for the auxiliary heater, within sight of the unit.
  3. Do not connect the auxiliary heater to the indoor unit circuit breaker.

Quick maintenance by error code: parts to check

Viessmann · DLFUAA indoor and outdoor units

Tables 8 to 11 list parts linked to each error code. The column alignment in the extracted text is not reliable, so use the printed page for part-to-code matching. Parts named in the tables: indoor PCB, outdoor PCB, indoor fan motor, outdoor fan motor, T1, T2, T2A, T2B, T3, T4 and TP sensors, pressure sensor, reactor, compressor, IPM module board, additional refrigerant, water-level switch, water pump, low pressure protector, high pressure protector, high pressure valve assembly, data adapter board, electric control box.

  1. Find the error code in the tables on pages 14 to 16.
  2. Check the listed parts for that code on the printed table.
  3. For some models the outdoor PCB cannot be removed alone. Replace the outdoor electric control box as a whole.

Reading the model number

Viessmann · DLFSAB and DLFLAB air handler units, sizes 18 to 60

DLF is the indoor unit, S&L is the model, and K means 208/230-1-60 voltage. The fan coil type letter A is the air handler and H is heat pump. The number after the type gives nominal capacity: 18 is 1 1/2 ton, 24 is 2 ton, 30 is 2 1/2 ton, 36 is 3 ton, 48 is 4 ton and 60 is 5 ton. Series and sequence are shown after that, along with week and year of manufacture and serial number.

Remote ON-OFF switch (CN2 and JR1)

Viessmann · 24V interface board CN2 and JR1

Remove jumper JR1 to enable remote ON-OFF control on CN2. An open switch turns the unit off. A closed switch turns it on, and the unit responds within 2 seconds. With the switch on, the remote or wired controller operates the unit normally. With the switch off, the unit ignores controller commands and displays the CP code on the board.

  1. Remove jumper JR1 on the 24V interface board.
  2. Wire the remote switch to CN2.
  3. Close the switch to allow operation, then test the response within 2 seconds.

UV LED output (CN43) 24 VAC

Viessmann · Main board CN43 UV LED terminal

Provides 24 VAC through a relay that closes while the fan runs. It can power a compatible UV LED light or a pilot relay with a 24 VAC coil to control other equipment.

  1. Connect a compatible UV LED or a 24 VAC pilot relay coil to CN43.
  2. Confirm the load is compatible with 24 VAC output.

Wait before servicing the PCB

Viessmann · DLFUAA indoor and outdoor PCBs

Capacitors keep a charge after power is off.

  1. Turn off all power and disconnect wires before working on the unit.
  2. Wear anti-static gloves or a wrist strap when checking the indoor or outdoor PCB.
  3. Wait five minutes after power is off before servicing the PCB, so the capacitors can discharge.

WORK contact (CN23) for blower status

Viessmann · Main board CN23 WORK terminal

Dry normally open output that follows the indoor blower. It is closed while the blower runs and open when it is off. The unit supplies no voltage here, so the external system must provide the power. Rated 250 VAC, 10 A maximum. If you need a 24 V signal, the G and C thermostat terminals can be used instead.

  1. Wire the external load to CN23 with its own power source.
  2. Keep the load within 250 VAC and 10 A.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.