Access & passwords: Mini-Split tips

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on access & passwords for mini-split. Check each one against the manual for your exact model before acting.

Enter engineering data mode (information inquiry)

Carrier · RG10 remote with D5FSCAH / D5FLCAH

Read live unit data through the RG10 remote. Use only the Power, Up, Down and OK buttons inside this mode.

  1. Make sure the unit is in standby or running normally, not locked.
  2. Press Power and Fan together for 7 seconds until the remote shows 0 and the mode icons appear.
  3. Press Up or Down to choose channel 0 to 30.
  4. Read the value on the indoor display. It shows the code for 2 seconds, then the value.
  5. To exit, press Power and Fan together for 2 seconds.

Lock or unlock the remote control

Carrier · D5FSOAH remote control RG10L5(2HS)

Locks or unlocks the wireless remote.

  1. Hold the BOOST and HUMIDITY buttons together for five seconds.

Operate the unit without the remote

Carrier · Indoor unit controls

If the remote is lost, the system can be run from the AUTO setting on the indoor unit. The indoor unit's MANUAL button cycles through AUTO, FORCED COOL and OFF.

  1. Press the MANUAL button on the indoor unit to select AUTO, FORCED COOL or OFF.

Remote ON-OFF input (CN23 and jumper JR6)

Carrier · D5FSOAH06XAK, D5FSOAH12XAK, D5FSOAH18XAK

Remove jumper JR6 to use the remote ON-OFF function. Open contact turns the system off and the display shows CP. Closed contact turns it on. The unit responds within 2 seconds.

  1. Remove jumper JR6 before wiring the remote switch to CN23.
  2. Leave the contact open to turn the system off (display shows CP).
  3. Close the contact to turn the system on.

Enter the wired controller settings menu

Viessmann · Wired remote KSACN0501AAA

Settings menu opens only with the system off. T1, T2, T26, T3 and T4 are thermistor sub-menus; do not select them when setting external static pressure.

  1. With the system OFF, press and hold COPY for about 4 seconds.
  2. Scroll with + or - and select SP or AF with CONFIRM.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.