Riello Boiler: Riello 40 F5 will not run or air shutter will not close
Riello 40 F5 will not run or air shutter will not close on a Riello boiler: The electronic air shutter runs on 120 V. The burner motor will not start until the shutter is fully open.
Applies to: Riello 40 F5 burner on Weil-McLain Ultra Oil UO-3, UO-4, UO-5
Common causes of riello 40 f5 will not run or air shutter will not close
- No constant 120 V on the AUX terminal of the sub-base
- Neutral and hot swapped
- Bad electronic air shutter
How to fix riello 40 f5 will not run or air shutter will not close: step by step
- Power off before opening the control box.
- Check for steady 120 V at the AUX terminal. Without it the burner will not run, or the shutter will not close after shutdown.
- Check that line and neutral are not reversed and the chassis is grounded.
- Check the safety limit and operating limit are separate and wired in series with the burner.
- If 120 V is there and the shutter does not move, replace the electronic air shutter (part 3020249; F5 replacement air damper kit C7001082).
Source: Riello 40 F3/F5 oil burner installation & operating manual C6501071 (Weil-McLain Ultra Oil edition), Internal factory wiring p.6; Application field wiring p.7; Setting the air adjustment plate p.11; Spare parts p.14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.