Riello Boiler: Riello 40 burner in lockout (red lamp on)
Riello 40 burner in lockout (red lamp on) on a Riello boiler: The 530 SE/C primary control locks out when it does not see flame after the oil valve opens. The lockout lamp is in the reset button.
Applies to: Riello 40 F5 burner on Weil-McLain Ultra Oil UO-3, UO-4, UO-5
Common causes of riello 40 burner in lockout (red lamp on)
- No oil to the nozzle (air in the pump, empty tank, plugged filter)
- Electrodes out of adjustment or bad ignition
- Dirty photocell
- Nozzle plugged or wrong
How to fix riello 40 burner in lockout (red lamp on): step by step
- Do not keep resetting. Each try sprays oil into the chamber. If oil has pooled in the chamber, clean it out before firing.
- Normal cycle: motor and ignition start, about 12 s of pre-purge, then the oil valve opens. If no flame is seen, the control locks out a few seconds later (about 5 s on the start-up chart). Check the chart on p.12 for the exact timing.
- Check oil supply: tank level, valves open, external filter clean.
- Purge air from the pump (see the pump purge guide).
- Power off. Pull the drawer assembly and check the electrode gaps (4 to 5 mm / 5/32 to 13/64 in.) and the nozzle.
- Check and clean the photocell.
- Reset once and watch a full cycle.
Source: Riello 40 F3/F5 oil burner installation & operating manual C6501071 (Weil-McLain Ultra Oil edition), Burner components p.2; Electrode setting p.8; Start-up cycle p.12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.