Updated · by Aurora Star Tech Inc.

Outdoor fan runs but compressor does not on a Rheem heat pump: Before opening the outdoor unit, kill the power at the disconnect and discharge the capacitor, because it can bite. On this Rheem 2-stage heat pump, the outdoor fan is turning but the compressor sits silent, maybe humming. A fan that runs tells you the contactor is pulling in and voltage is reaching the unit. So now you're down to the capacitors, the start relay, the connections and the compressor itself. Don't condemn the compressor until you've cleared the cheap parts and given a hot overload time to reset.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC

Common causes of outdoor fan runs but compressor does not

  • Bad run or start capacitor
  • Bad start relay
  • Loose connection at the contactor or compressor terminals
  • Compressor stuck, grounded, open winding or open internal overload
  • Low voltage at the unit

How to fix outdoor fan runs but compressor does not: step by step

  1. Shut off power at the disconnect, discharge and test the run and start capacitors and the start relay, and replace faulty parts
  2. With power on and the unit calling, check voltage at the compressor and tighten any loose connections, hot terminals or burnt wire ends mean a bad connection
  3. If the internal overload is open, wait at least 2 hours for it to reset before condemning the compressor
  4. Check winding resistance between the terminals and to ground with power off, an open reading or a ground reading means the compressor has failed
  5. Low voltage: correct the supply, start kit components are factory installed
  6. If the compressor is bad, refrigerant recovery and replacement is a job for a licensed technician
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rheem Heat Pump codes

Models

RPRL-024JECRPRL-036JECRPRL-048JECRPRL-060JEC

Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 18.6 General Troubleshooting Chart, p.47. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.