NTI General: Removing the boiler from a common vent system
Removing the boiler from a common vent system on a NTI general: Pull a boiler off a common vent and the remaining appliance is now on a vent sized for more. Spillage and CO risk. This check confirms the remaining appliance still vents properly. Do it every time a boiler comes off a common vent, and use the NFGC / ANSI Z223.1 rules.
Applies to: TRX150, TRX199, TRX199C
Common causes of removing the boiler from a common vent system
- A boiler removed from a shared flue during replacement or conversion
- Remaining appliance now on an oversized vent that may not draft well
- Existing vent damaged, blocked or corroded
- Building under negative pressure from fans and dryers
How to fix removing the boiler from a common vent system: step by step
- Seal any unused openings in the common vent.
- Inspect the vent for proper size, horizontal pitch, blockage, leakage, or corrosion.
- Close building doors and windows, close fireplace dampers, and run exhaust fans at maximum speed (not a summer exhaust fan). Run clothes dryers and other non-vented appliances.
- Run the remaining appliance continuously and test for spillage at the draft hood relief after 5 minutes with a match, candle or smoke.
- Return doors, windows, fans and dampers to normal after the test.
- Correct any improper common vent operation to meet NFGC / ANSI Z223.1.
- If you see spillage, do not leave the appliance running. Have a licensed tech resize or repair the vent.
Source: NTI TRX150 manual, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.