NTI General: Expansion tank and air elimination
Expansion tank and air elimination on a NTI general: What I usually see wrong on these jobs is air and the expansion tank. Closed-type systems depend on a correctly sized tank and a cushion of air in it, and that air has to be kept out of the piping. Bad sizing or an automatic air vent bleeding the system down gives you noisy pipes, pressure swings and relief valve discharge. These rules cover how to size and connect it.
Applies to: TRX150, TRX199, TRX199C
Common causes of expansion tank and air elimination
- New closed-type expansion tank system being sized
- Tank tied to the wrong side of the air separator
- Automatic air vents installed that bleed off the cushion
- No micro-bubble air elimination, so air stays in the loop
How to fix expansion tank and air elimination: step by step
- Size the expansion tank for total system volume, including all piping, fixtures and the boiler. Heat exchanger volume is 2.0 gal (TRX150) or 2.7 gal (TRX199/199C).
- Connect the tank to the air separator only if the separator is on the pump suction side.
- Install the system fill connection at the same point as the expansion tank connection.
- Install a micro-bubble air elimination device on every installation. Automatic air vents alone are not acceptable.
- Do not install automatic air vents on closed-type expansion tank systems. Air must stay in the system to form the air cushion.
- Check tank precharge against fill pressure before filling.
Source: NTI TRX150 manual, p. 25, 27. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.