NTI Boiler: Pressure test the gas supply

Updated · by Aurora Star Tech Inc.

Pressure test the gas supply on a NTI boiler: Most of the time a gas line gets pressure tested on a new install or after piping changes, and the boiler gets caught in the middle of it. The NTI TRX150 gas valve can only take so much. If the line test goes above 1/2 psi (14 in WC), the boiler and its shutoff valve have to be physically disconnected from the line. At or below 1/2 psi (3.5 kPa), closing the boiler's manual shutoff valve isolates it. Overpressure can damage the gas valve internals, and that is how you end up with a fire or an injury later, sometimes without any sign of trouble at the time of the test.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: TRX150 gas supply

Common causes of pressure test the gas supply

  • Test pressure above the gas valve limit of 1/2 psi
  • Boiler and shutoff valve left connected to the line during a high pressure test
  • Manual shutoff valve closed but leaking by, so pressure reaches the gas valve anyway
  • Test started before everyone on site knew the boiler was already piped in

How to fix pressure test the gas supply: step by step

  1. Confirm the planned test pressure first and decide whether it is above or at or below 1/2 psi (3.5 kPa).
  2. For tests at or below 1/2 psi, close the boiler's manual gas shutoff valve to isolate it.
  3. For tests above 1/2 psi, disconnect the boiler and its shutoff valve from the line and cap the open pipe.
  4. Watch the gauge for a few minutes and leak-check every joint with approved leak detector solution, never a flame.
  5. Bleed the test pressure down slowly before reconnecting anything.
  6. Do not fire the boiler until all connections are made and the heat exchanger is full of water.
  7. Have a licensed gas fitter do the test and the reconnection, and leak-check the boiler connection after reopening the valve.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: NTI Boiler codes

Models

TRX085TRX110CTRX150TRX199TRX199C

Source: NTI TRX150 manual, p. 55-56. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.