NTI Boiler: Exhaust vent and intake pipe installation rules
Exhaust vent and intake pipe installation rules on a NTI boiler: General rules for routing and joining vent pipe.
Applies to: Exhaust vent and intake pipe
How to fix exhaust vent and intake pipe installation rules: step by step
- Use only solid PVC, CPVC or stainless pipe, or polypropylene approved for Category IV. ABS is for air inlet only.
- Remove all burrs and debris from joints.
- Clean, prime and cement all PVC/CPVC joints with approved cement (ASTM D2564 for PVC, ASTM F493 for CPVC). Do not cement polypropylene.
- Slope horizontal exhaust back toward the boiler at least 1/4 in per foot.
- Support all piping. Use hangers at 4 ft intervals or less.
- Do not use the boiler to support any piping.
- Install roof flashing where pipe passes the roof.
- Keep the exhaust discharge pointing away from the roof pitch.
- Screen both terminations to keep out debris and birds.
- Do not vent over walkways, driveways or parking lots where condensate could freeze in cold climates.
If the unit shows an error code, look it up: NTI Boiler codes
Models
TRX085TRX110CTRX150TRX199TRX199C
Source: NTI TRX150 manual, p. 36-37. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.