NTI Boiler: Clean the heat exchanger combustion chamber

Updated · by Aurora Star Tech Inc.

Clean the heat exchanger combustion chamber on a NTI boiler: Remove the combustion assembly, clean the heat exchanger tubes, then reassemble with new seals. Use a nylon brush and an FDA approved lime scale remover. Do not use solvents. Protect the back wall insulation from water. Wear N95 respirator, gloves and eye protection, and wet the chamber lining to limit dust.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: TRX150

How to fix clean the heat exchanger combustion chamber: step by step

  1. Power off and close the gas supply before starting.
  2. Remove the silencer.
  3. Remove the gas diaphragm if one is fitted.
  4. Disconnect the electrode, igniter and blower electrical connections.
  5. Unscrew the two nuts and remove the gas pipe.
  6. Unscrew the four nuts on the burner door and remove it.
  7. Disconnect the condensate hose and siphon cap from the boiler, taking care as condensate may escape.
  8. Remove the blower and electrodes.
  9. Remove the combustion assembly.
  10. Check the back wall insulation and replace it if needed.
  11. Spray water or approved solution into the combustion assembly and watch each tube. Liquid must flow freely; if a tube is blocked, increase flow on that tube to force the blockage out.
  12. Check the burner for damage and replace it if needed. Replace the burner gasket whenever the burner is replaced.
  13. Replace any damaged or deteriorating gaskets.
  14. Check the combustion assembly sealing ring and replace it if damaged.
  15. Reassemble the combustion assembly and reinstall the electrodes and screws.
  16. Reconnect the gas line with a new sealing ring and reconnect the electrode wiring.
  17. Reinstall the silencer.
  18. Restore power and gas, restart the boiler, check the combustion system for gas leaks and observe for 5 to 10 minutes. Confirm condensate flows normally.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: NTI Boiler codes

Source: NTI TRX150 manual, p. 96-97. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.