NTI Boiler: Check inlet gas pressure at the boiler

Updated · by Aurora Star Tech Inc.

Check inlet gas pressure at the boiler on a NTI boiler: Use a manometer on the line pressure test point to confirm the inlet gas pressure is within the minimum and maximum for the gas type. Loosen the bolts before checking the inlet pressure. Do not change screws 2 and 4 (OFFSET and throttle) unless you have a calibrated combustion analyzer.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: TRX150 natural gas and LP

How to fix check inlet gas pressure at the boiler: step by step

  1. Turn off the gas supply and confirm the boiler is isolated if the test pressure will exceed 1/2 psi (14 in WC).
  2. Remove the yellow cap from the line pressure test point.
  3. Unscrew the P in screw.
  4. Connect the manometer to the test point.
  5. Read the inlet gas pressure and compare it to the gas pressure table.
  6. Disconnect the manometer.
  7. Tighten the P in screw.
  8. Leak-check the connection with an approved leak detector solution.
  9. Replace the yellow cap.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: NTI Boiler codes

Models

TRX085TRX110CTRX150TRX199TRX199C

Source: NTI TRX150 manual, p. 61. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.