Navien Tankless Water Heater: HotButton push button does not start recirculation (NaviCirc system)

Updated · by Aurora Star Tech Inc.

HotButton push button does not start recirculation (NaviCirc system) on a Navien tankless water heater: The HotButton starts a recirculation run only when someone pushes a button. NPE-A2/S2 heaters have the HotButton controller built in; the buttons, wall plates and temperature sensor are bought separately.

Homeowner with a tankless water heater problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: NaviCirc recirculation valve (PFFW-SXX-001) on Navien NPE-A/A2/S2, NPN water heaters and NCB-H/NFC-H combi boilers

Common causes of hotbutton push button does not start recirculation (navicirc system)

  • HotButton turned off on its DIP switch
  • Heater or boiler not set for recirculation / HotButton mode
  • Wiring too long, too thin, or on the wrong terminals
  • Metal plate still on SENSOR I when a temperature sensor was added

How to fix hotbutton push button does not start recirculation (navicirc system): step by step

  1. Safety: turn off power to the heater before you work on the controller wiring.
  2. HotButton DIP SW1: OFF = HotButton enabled (default). SW2: OFF = energy saver on (default); the energy saver limits run time and may be required by local code.
  3. The HotButton only works when the heater is set up for DHW recirculation. Other recirculation functions are disabled when it is used.
  4. NCB-H / NFC-H: DHW Recirculation must be External > HotButton (Manual).
  5. NPE-A: with a HotButton, P12 (pump cycle time) can be set to 5 minutes max.
  6. Wired buttons go to SIGNAL 2 (not polarity sensitive). SIGNAL 1 (12 V / GND / 5 V) is for wireless buttons or a motion sensor. Several buttons can share the same terminals or a common branch.
  7. Up to 10 buttons per controller. Use UTP cable or wire heavier than AWG 24, total cable no more than 328 ft (100 m). Use spade connectors.
  8. Temperature sensor: remove the metal plate from SENSOR I before connecting it. On NPN, insulate the sensor; its wire can be extended up to 100 ft with 22 AWG.
  9. Recirculation can also be started from the NaviLink app if the NaviLink WiFi kit is installed.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Tankless Water Heater codes

Models

NaviCirc

Source: Navien NaviCirc Installation and Operation Manual (navicirc-installation-and-operation-manual-en.pdf), p.16, 32-37, 52-53, 55-56, 65-68. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.