Navien General: Tank placement and condensate piping
Tank placement and condensate piping on a Navien general: Install the neutralizer tank so condensate flows by gravity from the appliance into the tank and on to the drain, with no backflow and no flue gas leakage.
Applies to: Large commercial condensate neutralizer tank, 7,000 MBTU/hr
How to fix tank placement and condensate piping: step by step
- Set the tank on a secure, level base.
- Make sure the tank inlet and outlet are lower than the appliance condensate drain.
- Connect the appliance condensate drain to the tank inlet using corrosion-resistant piping.
- Keep the condensate line out of any area exposed to freezing temperatures.
- Protect the piping from foot or vehicle traffic where damage is possible.
- Check that the piping has no air pockets and that condensate flows freely into the tank and out to the drain.
- Install a trap on every condensate drain to stop flue gas leakage.
- Make sure the connection between appliance and tank prevents condensate backflow into the appliance.
- Check local water authority rules before discharging treated condensate to the drain or sewer.
- Install unions at the inlet and outlet so the tank can be removed quickly when changing media.
If the unit shows an error code, look it up: Navien General codes
Source: Navien large commercial condensate neutralizer tank installation instructions, p. 1-2. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.