Navien General: Monthly maintenance of the neutralizer tank
Monthly maintenance of the neutralizer tank on a Navien general: The tank must be checked monthly and the media changed on schedule so condensate stays neutral enough to protect drains and the public sewer.
Applies to: Commercial condensate neutralizer tank
Common causes of monthly maintenance of the neutralizer tank
- Media exhausted or coated with precipitate
- Debris blocking the flow path
- Condensate pH dropped below the local minimum
How to fix monthly maintenance of the neutralizer tank: step by step
- Once a month, check the tank for cleanliness, media level and pH.
- Remove any precipitate coating or debris to prevent blockages.
- Check pH after condensate leaves the tank, or remove the lid and sample from the last chamber before the outlet.
- Use pH test strip paper or an electronic pH meter for an accurate reading.
- Replace the neutralizing media when pH falls below the local water authority minimum, or after one year, whichever comes first.
- For replacement media, contact the local Navien distributor.
If the unit shows an error code, look it up: Navien General codes
Source: Commercial condensate neutralizer tank installation instructions, p. 1. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.