Navien General: Monthly maintenance and media replacement
Monthly maintenance and media replacement on a Navien general: Check the tank monthly for debris, media level and pH. Replace the neutralizing media when pH falls below the local minimum or after one year, whichever comes first.
Applies to: Large commercial condensate neutralizer tank, 7,000 MBTU/hr
How to fix monthly maintenance and media replacement: step by step
- Once a month, check the tank for cleanliness and remove any debris to prevent blockages.
- Check the neutralizing media level.
- Check condensate pH after it leaves the tank, or lift the lid and sample from the last chamber before the outlet.
- Use pH test strip paper or an electronic pH meter for an accurate reading.
- Replace the neutralizing media when pH drops below the local water authority minimum, or after one year, whichever comes first.
- Order replacement media from a local Navien distributor (Replacement Media #GXXX002369).
If the unit shows an error code, look it up: Navien General codes
Source: Navien large commercial condensate neutralizer tank installation instructions, p. 1. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.