Navien General: Maintenance and pH check of neutralizing media
Maintenance and pH check of neutralizing media on a Navien general: Keep access to the discharge so the media can be tested. Check the pH at the outlet once a year with pH test strips or an electronic pH meter. Replace the media when pH falls below the local water authority minimum, or below 6.0 as a recommended limit. Check the media level in the unit periodically.
Applies to: Navien condensate neutralizer kit
Common causes of maintenance and ph check of neutralizing media
- Neutralizing media exhausted (pH low at outlet)
- Media level dropping in the housing
How to fix maintenance and ph check of neutralizing media: step by step
- Check the media level in the housing periodically.
- Test the pH at the outlet once a year.
- Replace the media if pH is below the local minimum or below 6.0.
- Use replacement media part GXXX001323.
If the unit shows an error code, look it up: Navien General codes
Source: Navien Condensate Neutralizer installation instructions, p. 2. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.