Navien Furnace: Vertical exhaust and combustion air termination layout
Vertical exhaust and combustion air termination layout on a Navien furnace: Terminal layout for vertical venting through a roof.
Applies to: NDF600 series furnaces, vertical venting
How to fix vertical exhaust and combustion air termination layout: step by step
- No termination fitting is needed when venting vertically through a roof.
- Set the exhaust pipe end 12 in (305 mm) higher than the combustion air intake terminal.
- Use a pair of medium or long sweep 90 degree elbows pointing downward on the combustion air intake.
- Locate the combustion air inlet at least 12 in (305 mm) above grade or expected snow level and 12 in (305 mm) below the exhaust outlet.
- Extend the exhaust pipe through the roof at least 18 in (457 mm) above any obstruction within an 18 in (457 mm) horizontal distance.
- Insulate all venting extending 24 in (610 mm) or more to the outside.
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NDF installation and operation manual, p. 31. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.