Navien Furnace: Vent termination clearances in the United States
Vent termination clearances in the United States on a Navien furnace: Minimum distances for the vent exhaust terminal in the United States.
Applies to: NDF600 series furnaces, installations in the United States
How to fix vent termination clearances in the united states: step by step
- Keep the bottom of the terminal at least 12 in (305 mm) above grade.
- Do not terminate over public walkways or where condensate or vapor could create a nuisance or hazard.
- Keep the terminal 4 ft (1.2 m) below, 4 ft (1.2 m) horizontally from, or 1 ft (305 mm) above any door, window, soffit, under eave vent or gravity air inlet.
- Keep at least 4 ft (1.2 m) horizontal clearance from electric meters, gas meters, regulators and relief equipment.
- Locate the terminal 3 ft (0.91 m) above any mechanical air inlet within 10 ft (3 m); a dryer or furnace make-up air inlet counts as a forced air inlet.
- Keep the terminal at least 3 ft (0.91 m) from an inside corner formed by two exterior walls.
- For overhangs, keep at least 1 ft (0.3 m) vertical clearance for each foot horizontal, up to 6 ft (1.8 m).
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NDF installation and operation manual, p. 29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.