Navien Furnace: Set manifold gas pressure (two-stage gas valve)
Set manifold gas pressure (two-stage gas valve) on a Navien furnace: Set low-fire and high-fire manifold pressure with a manometer on the outlet pressure boss. Always follow the values on the rating plate.
Applies to: Two-stage gas valve manifold pressure
How to fix set manifold gas pressure (two-stage gas valve): step by step
- Complete start-up and setup first. Turn off gas and power.
- Back the outlet pressure test screw out counterclockwise one turn maximum with a 3/32 in. Allen wrench, and attach a manometer hose (overlap 3/8 in., range at least 0 to 15 in. w.c.).
- Turn on gas and power. Energize the main solenoid by connecting R to W1. Do not energize HI.
- Remove the low outlet regulator adjust cover screw. Turn the plastic adjust screw clockwise to raise manifold pressure, counterclockwise to lower it. Set to the rating plate value and replace the cover screw.
- Energize the main solenoid and HI by connecting R/W1 and W1/W2. Remove the high outlet regulator cover screw. Adjust the same way to the rating plate value, then secure the cover screw.
- Turn off gas and power. Remove the hose and tighten the outlet pressure screw clockwise to at least 7 in-lb.
- Turn gas and power back on, energize the valve, and leak test the pressure boss screw with soap suds or leak solution.
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NDF installation and operation manual, p. 51 to 52. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.