Navien Furnace: Run the start-up wizard on first power-up
Run the start-up wizard on first power-up on a Navien furnace: The wizard must be finished before the furnace will run. Settings can be changed later from the Installer menu.
Applies to: All NPF700 models on first power-up
How to fix run the start-up wizard on first power-up: step by step
- Power on the furnace; the wizard starts automatically.
- Set the time and date, then the display units (°F/feet or °C/meters).
- Confirm the gas type (natural or propane).
- Set the installation elevation.
- Set the water fill type: water line connected (enabled) or manual fill (disabled).
- Set heat stage (1STG or 2STG) and cool stage (1STG, 2STG or No Cooling).
- Set heat control: supply or return air, supply set temperature, airflow control mode, heat airflow.
- Set cool appliance (AC or heat pump), tonnage, cool airflow per stage, and ramping profile.
- Set continuous FAN airflow and run the air test to set minimum and maximum airflow.
- Review the setup summary and press OK on each screen until the main screen appears.
If the unit shows an error code, look it up: Navien Furnace codes
More commissioning tips for furnace
Source: Navien NPF installation and operation manual, p. 101-102. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.