Navien Furnace: Measure inlet gas pressure
Measure inlet gas pressure on a Navien furnace: Licensed professional only. Furnace must have enough inlet gas pressure to run. Steps 2 to 7 are not on these pages.
Applies to: NPF700 hydro-furnace inlet gas pressure check
How to fix measure inlet gas pressure: step by step
- Shut off the manual gas valve on the gas supply line.
- Loosen the screw shown in the figure and connect a manometer to the pressure port.
- Zero the manometer before use.
- Reopen the manual gas valve and check all joints for leaks.
- Restart the furnace so the MAX setting runs the burner and fan at full capacity.
- At maximum firing rate, read the inlet gas pressure and confirm it is within the range for the gas type.
- Reinstall the upper front cover, seat it fully against the furnace, and tighten the three knobs clockwise.
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NPF installation and operation manual, p. 49-50. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.